Grounding
WARNING
FIRE AND EXPLOSION HAZARD
Before operating the pump, ground the
system as explained below. Also read
the section FIRE AND EXPLOSION
HAZARD on page 3.
1. Pump: connect the ground wire (A) firmly to a
metal part of the tank such as the base of the
carry handle (B). Connect the other end of the wire
to a true earth ground. See Fig. 1. Order Part No.
237569 Ground Wire and Clamp.
2. Air compressor: according to the manufacturer's
recommendations.
3. Object being sprayed: according to local code.
4. All solvent pails used when flushing, according to
local code. Use only metal pails, which are con-
ductive. Do not place the pail on a non-conductive
surface, such as paper or cardboard, which inter-
rupts the grounding continuity.
4
307133
Installation
5. To maintain grounding continuity when flushing or
relieving pressure, always hold a metal part of the
gun firmly to the side of a grounded metal pail,
then trigger the gun.
Fig. 1
A
B
7856