The TAE DI4 -C (Fig. 1) is a room electronic thermostat suitable
for a reliable and accurate temperature regulation in commercial
and industrial premises as well as for home installation. The digital
display gives the readout of the room temperature, thus allowing
an accurate regulation of the temperature in the environment to be
controlled. The manual selector (a) selects the heating or cooling
mode, according to the type of the plant wired to the thermostat.

Features

• 230V~ (TAE-DI4-MC) or 24V~/= (TAE-DI4-2C) power supply
• Knob limitation feature through mechanical pins
• Room temperature display
• Heating / Cooling switch
• Fixing with distance between holes 60mm
• Compliant with directives EEC 89/336, 73/23 and 93/68 CE

Model Types

Technical Data

Online store: www.syxthsense.com
Enquiries: T: 0870 20 80 100 F: 0870 20 80 200
Model
Description
TAE-DI4-MC
Electronic Room Thermostat with Display
TAE-DI4-2C
Electronic Room Thermostat with Display (24Vac)
Power supply
TAE-DI4-MC
TAE-DI4-2C
Power absorption
7VA
Regulation range
6°C...30°C
Sensor type
PTC 2k ohm @ 25°C internal
Remote sensor
Cod. STL PTS A150
(optional)
Accuracy
Thermostat
Display
Resolution
Knob
Display
Hysteresis
0,5°C
Contact rating
5 (1) A @ 250V~ SPDT
Protection class
IP30
Operating
0°C...40°C
temperature
Storage temperature
-10°C...+50°C
Humidity limits
20%...80% rH (non condensing)
Enclosure
Material: ABS V0 self-extinguishing
Colour: Signal white (RAL 9003)
Size
85W x 85H x 31D mm
Weight
~150 gr.
Thermostat type
230V~ -15% +10% 50Hz
24V~/= -15% +10% 50Hz
±1°C
±1°C (0°C...30°C range)
1°C
0.1°C
Product sheet TH6.12
TAE-DI4
PS TH6.12 - 1/4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TAE-DI4 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SyxthSense TAE-DI4

  • Page 1 The manual selector (a) selects the heating or cooling mode, according to the type of the plant wired to the thermostat. Features • 230V~ (TAE-DI4-MC) or 24V~/= (TAE-DI4-2C) power supply • Knob limitation feature through mechanical pins • Room temperature display •...
  • Page 2 SyxthSense Ltd OPERATION If the device is in ‘Heating’ mode and the measured room temperature is below the value set with the knob the thermostat turns the relay on and, at the same time, turns the flame symbol on the display.
  • Page 3 SyxthSense Ltd WARNING: To adjust properly room temperature, install the thermostat far from heat sources, draughts or particularly cold walls (thermal bridges). When the remote sensor is used in conjunction with the thermostat, then this note is to be applied to the remote sensor itself.
  • Page 4 SyxthSense Ltd Online store: www.syxthsense.com © 2003 SyxthSense Ltd. All rights reserved - 07/2004 Enquiries: T: 0870 20 80 100 F: 0870 20 80 200 PS TH6.12 - 4/4...

Table of Contents