Summary of Contents for SyxthSense NEW WAVE DTP Series
Page 1
NEW WAVE TERMOSTATO AMBIENTE VIA RADIO WIRELESS ROOM THERMOSTAT RADIORAUMTHERMOSTAT THERMOSTAT D’AMBIANCE PAR RADIO TERMOSTATO AMBIENTE VÍA RADIO TERMÓSTATO AMBIENTE VIA RÁDIO ...
Page 4
Fig. 5 - Abb. 5 Ponticello JP1: selezione sonda temperatura ambiente Jumper JP1: selection of room temperature probe Brücke JP1: Auswahl Raumtemperatursonde Pont JP1 : sélection de la sonde de température ambiante Puente JP1: selección sonda temperatura ambiente Jumper JP1: selecção da sonda de temperatura ambiente Sonda interna abilitata (default) - Internal probe enabled (default) Innensonde aktiviert (Default) - Sonde intérieure activée (par défaut)
Page 6
NOTA: Dopo aver modificato i ponticelli è consigliabile forzare un aggiornamento entrando e uscendo dalla funzione “Test” (premendo 2 volte il pulsante test indicato con In alternativa, modificare i ponticelli prima di inserire le batterie. NOTE: After having modified the jumpers, it is recommended to force an update by entering and exiting the “Test”...
MAIN FEATURES • Operating frequency 868.150 MHz • Redundant transmission by radio command with selectionable transmission time • Internal sensor and input for remote sensor • Possibility of locking or limiting the knob • Low battery indicator • Heating/Cooling selection can be managed by the thermostat or on the receiver TECHNICAL FEATURES Power supply:...
Page 8
Modulation: GFSK Type of antenna: Internal Max. distance from receiver: >300 m in free field >50 m in buildings (depending on the building and environment) Protection rating: IP 30 Operating temp.: 0°C .. 40°C Storage temp.: -10°C .. +50°C Humidity limits: 20% ..
OPERATION Heating/cooling mode By adjusting the JP3 connector, shown by in Fig. 5, the thermostat can be set in Heating or Cooling mode: - Heating Jumper inserted to the left (F of Fig. 5) - Cooling Jumper inserted to the right (G of Fig. 5) Periodically the thermostat transmits a radio command to the receiver containing the information about the room temperature, setpoint temperature and the heating/cooling status.
Page 10
Selecting the sampling interval To make sure that the batteries last for a long time, the thermostat waits for a length of time between one transmission and another that can be chosen as 3 or 10 minutes by adjusting on an internal jumper JP2, shown by in Fig.
maximum length of wires allowed. Knob Using the regulation knob (Fig. 1), the setpoint temperature can be set around which the temperature check will be carried out in the range of 6°C .. 30°C. Limiting the rotation of the knob The field within which the knob rotates can be reduced by adjusting in the following way: - Lifting the knob by using a screwdriver as a lever in the appropriate guide...
Page 12
that the receiver correctly receives its signals. The operation is carried out by enabling the “Test” function, described below. Open the thermostat, as shown in the “Installation” paragraph, and insert the batteries while respecting the correct polarity; in (Fig. 5) the internal position of the batteries can be seen.
the relative documentation for further information. INSTALLATION Before installing the thermostat, make sure that the radio signals transmitted are correctly received by the receiving unit. We hereby remind you that the thermostat should be installed away from sources of heat, drafts and particularly cold or hot walls for the correct regulation of the room temperature.
plastic teeth click. - Reinsert the knob by positioning it in the right angle so that it correctly comes into connect with its spindle and then pressing it down to the bottom. TROUBLESHOOTING SYMPTOM: In the “heating” mode, even though the setpoint knob is on maximum, the red LED still remains OFF and the relative output in the receiver also remains...
Page 15
recently, it is possible that a small amount of energy is still present even if there is no power supply, therefore the thermostat momentarily behaves as if the batteries had not been removed at all. REMEDY: Press the internal test button for a second to reset the internal electronic circuits.
Page 16
WARNING - To determine the correct position one must ensure that the radio signals transmitted are correctly received by the receiving unit. - To adjust properly room temperature, install the thermostat far from heat sources, airstreams or particularly cold walls (thermal bridges). When the remote sensor is used in conjunction with the thermostat, then this note is to be applied to the remote sensor itself.
Need help?
Do you have a question about the NEW WAVE DTP Series and is the answer not in the manual?
Questions and answers