York YAFS012-018 Manual page 56

Table of Contents

Advertisement

Contractor:
Engineer:
Project Name:
Wiring Schematics cont.
Aurora Advanced with 5-Speed ECM
Slow Flash
1 second on and 1 second off
Fast Flash
100 milliseconds on and 100 milliseconds off
Flash Code
100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Fault LED (LED 1, Red)
Normal Mode
OFF
Input Fault Lockout
Flash Code 1
High Pressure Lockout
Flash Code 2
Low Pressure Lockout
Flash Code 3
Freeze Detection - FP2
Flash Code 4
Freeze Detection - FP1
Flash Code 5
Reserved
Flash Code 6
Condensate Overflow Lockout
Flash Code 7
Over/Under Voltage Shutdown
Flash Code 8
Future Use
Flash Code 9
Compressor Monitoring
Flash Code 10
Fault- FP1
Flash Code 11
Future Use
Flash Code 12
Non-Critical AXB Sensor Error
Flash Code 13
Critical AXB Sensor Error
Flash Code 14
Alarm - Hot Water
Flash Code 15
Fault Variable Speed Pump
Flash Code 16
Future Use
Flash Code 17
Non-Critical Communication Error
Flash Code 18
Fault - Critical Communication Error
Flash Code 19
Alarm - Low Loop Pressure
Flash Code 21
Fault - Communication ECM Fan Motor Error Flash Code 22
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.
SD2500AK6
06/21
P.O.:
Unit Tag:
AXB BOARD
Aurora LED Flash Codes
Random Start Delay (Alternating Colors)
Status LED (LED1, Green)
Configuration LED (LED 2, Yellow)
Fault LED (LED 3, Red)
Configuration LED (LED 2, Yellow)
No Software Overide
DIP Switch Overide
Status LED (LED 3, Green)
Normal Mode
Control is Non - Functional
Test Mode
Lockout Active
Dehumidification Mode
Future Use
Future Use
Load Shed
ESD
Future Use
Fault LED (LED 1, Red) Cont.
Alarm - Home Automation 1
Alarm - Home Automation 2
Fault - EEV Error
5 SPEED ECM MOTOR LOW VOLTAGE CONNECTIONS SINGLE SPEED
Model
TAP-1
22
30
BLUE
36
BLUE
42
BLUE
Fast Flash
48
BLUE
Fast Flash
60
BLUE
Fast Flash
70
BLUE
5 SPEED ECM MOTOR LOW VOLTAGE CONNECTIONS DUAL CAPACITY
OFF
Model
TAP-1
Slow Flash
26
BLUE
38
BLUE
49
BLUE
ON
64
BLUE
OFF
72
BLUE
Slow Flash
Fast Flash
Flash Code 2
Flash Code 3
Flash Code 4
Flash Code 5
Flash Code 6
Flash Code 7
Flash Code 23
Flash Code 24
Flash Code 25
56
Affinity & Affinity Advanced Series
1 - 6 Tons 60Hz
TAP-2
TAP-3
TAP-4
TAP-5
BLUE
RED
GRAY
RED
GRAY
RED
GRAY
RED
GRAY
RED
GRAY
RED
GRAY
RED
GRAY
TAP-2
TAP-3
TAP-4
TAP-5
RED
TAN
GRAY
RED
TAN
GRAY
RED
TAN
GRAY
RED
TAN
GRAY
RED
TAN
GRAY
Page _____ of _____