2) Ceiling height
Select the appropriate ceiling height according to the place of installation.
Function number
20
For the specific height for each setting value, refer to "Installation space" in Chapter 2.
on page 4.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
3) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function number
22
4) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 26°C and the setting value is "03"
(-1.0°C), corrected temp. will be 27°C (26°C - [-1.0°C]).
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er's recommended value).
Function number
30
(For cooling)
9-2. Function settings by using remote controller
Setting value
00
01
Setting value
00
01
Setting value
00
01
02
03
04
05
06
07
08
31
(For heating)
09
10
11
12
13
14
15
16
17
Setting description
Standard
High ceiling
Setting description
4-way
3-way
Setting description
Standard setting
No correction 0.0 °C
-0.5 °C
-1.0 °C
-1.5 °C
-2.0 °C
-2.5 °C
-3.0 °C
-3.5 °C
-4.0 °C
+0.5 °C
+1.0 °C
+1.5 °C
+2.0 °C
+2.5 °C
+3.0 °C
+3.5 °C
+4.0 °C
- 24 -
Factory setting
"Dimensions"
Factory setting
Factory
setting
More cooling
Less heating
Less cooling
More heating
9. Function settings