16.4. Outdoor Fan Control

16.4.1. Cooling Mode

Normally the system will choose the running fan speed according to ambient temperature:
When low ambient cooling is valid:
Outdoor fan speed control logical (low ambient cooling).
When T4 <15°C (59°F) and T3 < 30°C (86°F), the unit will enter into low ambient cooling mode. The outdoor fan will choose
speed according to T3.
When T3≥38°C (100.4°F) or when T4≥20°C (68°F), the outdoor fan will choose the speed according to T4 again.
T4
A
DC_FAN_HI_SPD_ADD
28℃
26℃
B
DC_FAN_MID_SPD_ADD
25℃
23℃
C
DC_FAN_MIN_SPD_ADD
22℃
20℃
D
DC_FAN_SLOW_SPD_ADD
19℃
17℃
E
DC_FAN_SSLOW_SPD_ADD
High
27
25
20
Low
15
low ambient cooling
Exit low ambient cooling
mode
,
run with high fan
38
for 1 minute
27
Low
off
36
30
23