3 Commissioning checklist
Work
92
Zone activated
93
Day temperature
94
Set-back temp.
95
Room temperature
96
Zone assignment
97
Zone valve status
98
ZONE2
99
Zone activated
100
Day temperature
101
Set-back temp.
102
Room temperature
103
Zone assignment
104
Zone valve status
105
Domestic hot water
106
Cylinder active
107
Target flow temp.
108
Domestic hot water
109
Current cyl. temp.
110
Cyl. charging pump
111
Circulation pump
112
Anti-legionella day
113
Anti-legionella time
114
Cyl. boost hysteresis
115
Cylinder boost offset
116
Max. cyl. charg. time
117
DHW req. anti-cy time
118
Ch. pump overrun time
119
Parallel cyl. charging
Menu → Installer level → Service information
120
121
Enter contact details
122
Service date Next service on
End user menu
Menu → Basic settings → Enter zone name → ZONE1 → Change
123
Menu → Basic settings → Enter zone name → ZONE2 → Change
124
Menu → Desired temperatures → ZONE1
125
126
Day temp. heating
127
Day temp. cooling
128
Set-back temp. heat.
129
Room temperature
Menu → Time programmes → ZONE1
130
131
HEATING 1: Cooling
132
Domestic hot water
133
Circulation
6
Comments/settings
Current value display: No / Yes
20 °C
15 °C
Current value display
VRC 700
Current value display (closed/open)
Current value display: No / Yes
20 °C
15 °C
Current value display
VR91 ad.1
Current value display (closed/open)
Condition: Domestic hot water cylinder in the system
Current value display
60 °C
Inform the end user about the anti-legionella function
Current value display
Current value display: off / On
Current value display: off / On
Select: off, Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, Sunday, Monday -
Sunday
Factory setting: off
04:00
5 K
25 K
45 min.
30 min.
5 minutes
off
Telephone number/company
Maintenance interval: 1 year
Implement the settings for the end user/inform the end
user
Enter a suitable name for the zone, e.g. Flat 1
(In consultation with the customer)
Enter a suitable name for the zone, e.g. Flat 2
(In consultation with the customer)
Zone1 (name after being renamed)
20 °C
24 °C
15 °C
Current value display
Changed the time schedule for Zone 1 (name after being
renamed) following consultation with the customer
Zone 1 = heating circuit 1
change following consultation with the customer
change following consultation with the customer
change following consultation with the customer
System installation instructions 0020257196_01