Taco 0034e Instruction Sheet

Taco 0034e Instruction Sheet

Ecm high-efficiency circulator

Advertisement

Quick Links

SUPERSEDES: NEW
Plant ID No. 001-5019
DESCRIPTION:
The 0034e is a high performance, variable speed, high-efficiency, wet-rotor circulator
with an ECM, permanent magnet motor. With 5 easy settings, its variable speed
performance curves are equivalent to the Taco 009, 0010, 0011, 0012, 0012 3-Speed,
0013, 0013 3-Speed & 0014. Ideal for large residential and light commercial hydronic
heating, chilled water cooling and domestic hot water systems. The 0034e reduces
power consumption by up to 85% compared to equivalent AC permanent split
capacitor circulators.
APPLICATION:
• Maximum operating pressure: 150 psi (10.3 bar)
• Minimum NPSHR: 18 psi at 203˚F (95˚C)
• Maximum fluid temperature: 230°F (110˚C)
• Minimum fluid temperature: 14°F (-10˚C)
• Electrical specifications:
Voltage: 115/208/230V, 50/60 Hz, single phase
Maximum operating power: 170W
Maximum amp rating: 1.48 (115V) / .70 (230V)
• Equipped with a cast iron or stainless steel casing
• SS Model suitable for open loop potable water systems
• Taco circulator pumps are for indoor use only – employer uniquement a l'interieur
• Acceptable for use with water or maximum of 50% water/glycol solution
FEATURES:
• Five easy dial settings to match system requirements - activeADAPT, LOW, MEDIUM, HIGH or 0-10V input
• Replaces all single speed and 3-speed circulators in its class
• ECM performance equivalent to Taco's 009, 0010, 0011, 0012, 0013 & 0014 circulators
• Multi-color LED display showing power on, mode setting and error code diagnostics
• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation
• Nut capture feature on flanges for easier fit up
• Dual electrical knockouts and removable quick-connect terminal strip for easy wiring
• Double insulated
• Whisper quiet operation
• BIO Barrier® protects the pump from system contaminants
• SureStart® automatic unblocking and air purging mode
• Rotatable Control Cover to allow any pump body orientation
INSTALLATION:
WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
AVERTISSEMENT : Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment
voids the warranty. Consult factory for fluid compatibility.
ATTENTION : L'ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un
équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent
pump cavitation and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure.
A larger size expansion tank may be required.
ATTENTION : Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée de 20 psi
au minimum afin d'éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression
du réservoir d'expansion de façon qu'elle soit égale à la pression de remplissage. Un réservoir d'expansion d'une taille supérieure
peut être nécessaire.
Instruction Sheet
-1-
102-543
EFFECTIVE: November 15, 2019
Figure 1
Standard flange model: 0034e-F2
Certified to
NSF/ANSI 61 & 372

Advertisement

loading

Summary of Contents for Taco 0034e

  • Page 1 • ECM performance equivalent to Taco’s 009, 0010, 0011, 0012, 0013 & 0014 circulators • Multi-color LED display showing power on, mode setting and error code diagnostics • Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation • Nut capture feature on flanges for easier fit up •...
  • Page 2 ZONE 1 ZONE 2 ZONE 3 FC - Optional Location KEY: VI, V2, V3 = SHUT-OFF ISOLATION VALVE P = TACO 0034e CIRCULATOR FF = FAST FILL BOILER FEED VALVE PV4 = PURGE VALVE MOD CON FC = FLOW CHECK VALVE...
  • Page 3 PREFERRED PRIMARY / SECONDARY PIPING FOR ZONE VALVES ON BOILER SUPPLY ZONE 1 ZONE 2 ZONE 3 KEY: VI, V2, V3 = SHUT-OFF ISOLATION VALVE P = TACO 0034e CIRCULATOR FF = FAST FILL BOILER FEED VALVE MOD CON PV4 = PURGE VALVE BOILER ZV = ZONE VALVE...
  • Page 4 Figure 4 — Acceptable Mounting Positions Figure 5 — Unacceptable Mounting Positions Flow Flow Figure 6 — Rotating Control Cover The 0034e is equipped with a symmetrical control cover connected to the Flow pump with a ribbon cable. The cover can be removed,...
  • Page 5 Connect Line/Hot power to the L terminal, Neutral to the N terminal and Ground to the G terminal. See wiring diagram above. The 0034e is a double insulated circulator; grounding wire is not necessary but recommended for safety. Replace terminal box cover. Insert rubber cap plug provided to cover unused knockout hole.
  • Page 6 6. Programming your 0034e circulator: Modify the performance of the circulator as needed by rotating the dial using a flat screwdriver. When the circulator is powered on, the LED will illuminate and change color based on the operating mode selected. The LED will flash each time a setting is changed. See diagram below to set pump for desired operating mode.
  • Page 7 0034e High-E ciency Circulator activeADAPT Range Purple LED activeADAPT™ Mode: activeADAPT is an operating mode designed for constant circulation systems. On this setting, the circulator will sense changes in system flow and head conditions and adjust the operating curve automatically. See activeADAPT activeADAPT operating range in the chart to the right.
  • Page 8 Fixed Speed Mode: At High Setting the circulator always Maximum Curve - Fixed Speed operates at full speed. 0034e High-E ciency Circulator HIGH Head = 34 ft. Blue LED Flow Rate Q [GPM] HIGH Power Consumption Maximum Curve 0034e High-E ciency Circulator...
  • Page 9 External connection for 0-10V DC / PWM signal WARNING: If there is a need to make external connection (PLC / Pump Controller) it is mandatory to perform the following operations. 1. Remove the four screws (Figure 8 - Ref. 1) attaching the control cover (Figure 8 - Ref. 2). 2.
  • Page 10: Analog Input

    0-10V DC Input Mode: PWM (Pulse Width Modulation) The circulator will vary its speed and performance based on a 0-10V DC 0034e High-E ciency Circulator analog signal external input. 100% 0-10V DC Performance Yellow LED 0-10V...
  • Page 11 Power Consumption 0034e High-E ciency Circulator Yellow LED 0-10V DC 0-10V 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 44 46 48 Flow Rate Q [GPM] Troubleshooting the error codes: Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction.
  • Page 12: Replacement Parts List

    Control Panel Cover (0034e Dial Version) 198-3247RP Terminal Box Cover 198-3185RP Wiring Connector (Green) 198-217RP Terminal Box cover screws (5 per bag) 0034e Pump Replacement Cross Reference (6-1/2” Flange to Flange Dimension) Taco Bell & Gossett Armstrong Grundfos Wilo 2400-10...