Control Strategy
OUTDOOR RESET
In order to properly control a hot water heating system, the heat supplied
to the building must equal the heat lost by the building.
• The heat supplied to a building is proportional to the temperature of the
supply water and the surface area of the heating element. A small surface
area such as baseboard radiators requires a higher water temperature
than a larger surface area such as radiant floors.
• The heat lost from a building is dependent on the outdoor temperature,
as well as other factors. As the outdoor temperature drops, the building
heat loss increases.
Instruction Sheet
PC702–1 Two Stage Boiler
Reset & DHW Control
June 1, 2000
The PC702-1 is a microprocessor-based control designed to regulate the supply water temperature
from a two stage boiler system based on the outdoor temperature or DHW requirements. A wiring
harness is provided to be easily connected to the Taco Expandable (-EXP) Controls.
The PC702-1 includes functions such as automatic reset ratio calculation, Warm Weather Shut Down
(WWSD), Minimum Boiler setting, adjustable interstage delay setting, optional boiler rotation, and an
optional automatic boiler differential. The control has a digital, liquid crystal display (LCD) that nor-
mally displays the Boiler Supply temperature, but can display other temperatures and settings.
Control Strategy . . . . . . . . . . . .
Sequence of Operation . . . . . . .
Installation . . . . . . . . . . . . . . . . .
Settings . . . . . . . . . . . . . . . . . . .
Press & Hold:
Item, to view settings
, to test
Press & Release:
Item +
+
OUTDR
Start
DHW
Item
Demand
1
2
Stage
1
1
Output
Boiler
Output
Boiler
pg. 1
pg. 2
pg. 4
pg. 5
Power:
24 V ±10% 50/60 Hz 3 VA
Relays:
120 V (ac) 5 A 1/6 hp pilot 240 VA
Demand:
20 to 260 V (ac) 2 VA
Jul 00
31000265
to adjust menu
VIEW
°F
1 2
DHW
Boiler
Delay
Demand
Demand
Interstage
®
C
US
PC702-1
158033
Do not apply power
Signal wiring
3
4
5
6
7
must be rated
Made in
Stage
Com Sup Out
at least 300V
Canada
2
2
Outdoor
Temperature
Drop
102-106
EFFECTIVE: March 1, 2004
Control Adjustments
Troubleshooting
. . . . . . . pg. 7
Error Messages. . . . . . . . . . . pg. 8
Technical Data . . . . . . . . . . . pg. 8
To Taco
Zone
Control
Input
OutdoorSensor
Included
Input
Boiler Sensor
Included
Constant
Room Temperature
. . . . pg. 6
Heat
Loss
Increase