Minimum Cooling Water Requirements - Beko DRYPOINT RS 25-1010 HP50 Instructions For Installation And Operation Manual

High pressure compressed air refrigeration dryer
Table of Contents

Advertisement

Installation
8.6

Minimum cooling water requirements:

Temperature
Pressure
Delivery pressure
Total hardness
PH
Conductivity
Residual solids
Saturation mark SI
HCO
3
2-
SO
4
Note:
(1) – Other temperatures upon request – check the data on the name plate.
(2) – Other pressures upon request – check the data on the name plate.
(3) – Pressure difference at the water connection of the dryer at maximum water flow.
Other delivery pressures upon request.
CAUTION!
During the piping of the dryer, the inlet and outlet connections need to be supported as is shown in the
illustration.
Non-observance will cause damage.
18
15 ... 30°C (1)
3...10 bar(g) (2)
> 3 bar (2) (3)
6.0...15 dH°
7.5...9.0
10...500 μS/cm
<30 mg/l or ppm
-0.2 < 0 < 0.2
70...300 mg/l or ppm
<70 mg/l or ppm
HCO
/ SO
>1.0 mg/l or ppm
3
4
NH
<2 mg/l or ppm
3
-
Cl
<50 mg/l or ppm
Cl
<0.5 mg/l or ppm
2
H
S
<0.05 mg/l or ppm
2
CO
<5 mg/l or ppm
2
NO
<100 mg/l or ppm
3
Fe
<0.2 mg/l or ppm
Al
<0.2 mg/l or ppm
Mn
<0.1 mg/l or ppm
DRYPOINT® RS 25-1010 HP50