GENERAL INSTRUCTIONS

1) Begin
the
installation
determining mounting options.
2) The slotted, circular keyways can be used to
secure the mounting plate to a standard
junction box.
The junction box must be
secured sufficiently to handle the weight of
the unit.
3) Additionally, three slotted vertical keyway
slots (Figure 1) may be used to attach the
mounting plate to independent anchor
supports.
Use three #8 toggle bolts
(supplied by others) for securing to
wallboard or hollow concrete walls. If the
wiring is wall recessed, run wires through
center hole of mounting plate in preparation
for unit wiring.
4) If desired, wall mounting can also be
accomplished with use of the optional
mounting shelf (See Optional Mounting
Shelf and Figure 2).
Figure 1
HOOKUP INSTRUCTIONS
Standard Units:
Connect A.C. service to unit charger leads:
Blue = 277 VAC
Black = 120 VAC
White = Common
Green = Ground
Philips Lighting North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873, USA
Phone: 855-486-2216
www.philips.com/luminaires
process
by
1. Connect remote lamps, if applicable, to
orange and yellow flying leads connected to
RL+ and RL- respectively. Ensure total unit
load (including internal lamps) does not
exceed unit rating.
2. Adjust head(s) to illuminate desired area(s).
3. Close cover and screw shut.
electrical wires and membrane switch cable
remain inside unit and that the cover does
not pinch wires when closed. Hand-tighten
two thumb nuts to finalize cover closure.

INSTALLING BATTERIES

1. Units may ship without batteries installed
depending on the wattage of the unit. For
lead units, battery wiring harnesses are
already connected to PCB assembly and
connection to the batteries is required. In
the case of Nicad units, connection of
battery harness to the PCB is required.
2. Install and wire batteries as appropriate.
(See Page 5 for battery configurations)
3. Tighten straps to secure batteries inside unit.
OPTIONAL MOUNTING SHELF
1. If the unit is to be mounted to poles,
columns or I-Beams, use the optional
mounting shelf and strapping kit (ordered
separately).
Figure 2
2. Once mounting shelf is installed, the unit is
ready for installation.
3. Place unit on shelf and secure with three (3)
securing screws (supplied with mounting
shelf) to shelf threaded inserts.