GENERAL INSTRUCTIONS

1) Begin
the
determining mounting options.
2) The slotted, circular keyways can be used to
secure the mounting plate to a standard
junction box.
secured sufficiently to handle the weight of
the unit.
3) Additionally, three slotted vertical keyways
may be used to attach the mounting plate to
independent anchor supports. Use three #8
toggle bolts for securing to wallboard or
hollow concrete walls. If the wiring is wall
recessed, run wires through center hole of
mounting plate in preparation for unit
wiring.
HOOKUP INSTRUCTIONS
Standard Units:
Connect A.C. service to unit charger leads:
Blue = 277 VAC
Black = 120 VAC
White = Common
Green = Ground
1. Connect remote lamps, if applicable, to
orange and yellow flying leads connected to
RL+ and RL- respectively. Ensure total unit
load (including internal lamps) does not
exceed unit rating.
2. Adjust head(s) to illuminate desired area(s).
Chloride is a Philips group brand
installation
process
The junction box must be
Pg -2-
3. Close cover and screw shut.
electrical wires and membrane switch cable
by
remain inside unit and that the cover does
not pinch wires when closed. Hand tighten
two thumb nuts to finalize cover closure.

INSTALLING BATTERIES

1. Units may ship without batteries installed
depending on the wattage of the unit. For
lead units, battery wiring harnesses are
already connected to PCB assembly and
connection to the batteries is required. In
the case of Nicad units, connection of
battery harness to the PCB is required.
2. Install and wire batteries as appropriate.
(See Page 6-7 for battery configurations)
3. Tighten straps to secure batteries inside unit.
OPTIONAL MOUNTING SHELF
1. If the unit is to be mounted to poles or
columns, use the optional mounting shelf kit
(ordered separately).
2. Once mounting shelf is installed, the unit is
ready for installation.
3. Place unit on shelf and secure with three (3)
securing screws to shelf threaded inserts.
OPERATING INSTRUCTIONS
1. Normal Power-Up Sequence
At power-up, the red and green LED
indicators will alternately flash for one to
two seconds. Next, the unit will go through
a "Power-up Quick Test" with the green
LED flashing quickly. If no power-up faults
are detected, the green LED will then flash
slowly for approximately 36-72 hours to
indicate the unit is in a high rate of charge.
9140053340 Rev. 0