Figure 6 shows the connections to
a transformer (lighting or distribu-
tion).
Make sure that the switches and/
or circuit breakers on both sides
are open.
Check the high voltage winding to
ground, low voltage to ground, and
the resistance between them with
no winding grounded.
-
!
Battery
Check
AEMC
I N S T R U M E N T S
Quality AEMC Products Online at:
Megohmmeter Models 1005 and 1015
Jumpers
~
~
~
~
~ ~
+
600V
6
OFF
MΩ - 500 V
MΩ - 1000 V
1000 Ω
10 Ω +
10 Ω −
MEGOHMMETER
MODEL 1015
GlobalTestSupply
Figure 7
www.
Transformer
Grounding Lug
-
+
600V
!
6
Battery
OFF
MΩ - 500 V
Check
MΩ - 1000 V
1000 Ω
10 Ω +
10 Ω −
MEGOHMMETER
AEMC
MODEL 1015
I N S T R U M E N T S
Figure 6
Figure 7 shows the connections for
measuring the insulation of a three-
phase line to ground by connecting
the jumpers between phases.
This gives a reading of all conductors
at once. If a load such as a motor,
heater, etc., is attached to the other
end of the line, it will read the load
resistance to ground at the same
time.
By removing the jumpers, readings
can be made between the individual
conductors and ground.