CS-F34DB4E5 CU-L34DBE5 / CS-F43DB4E5 CU-L43DBE5
9.3.6.
Drain pump control
• • • • During cooling, dry, or defrost operation, drain pump operate by following the below table.
• • • • When compressor start, drain pump operation start after 10 second of indoor fan starting.
• • • • When operation stop or thermostat is off, drain pump continue operating for 6 minute to prevent the drain water from coming
back.
9.3.7.
Cooling low temperature protection control
• • • • During cooling, or dry operation, if outdoor temperature is less than -15°C.
− − − − And thermostat on condition continue for 15 min, compressor stop.
− − − − After 3 min waiting (restart delay), if thermostat is on, compressor restart.
9.4.
Heating Mode Operation
9.4.1.
Heating indoor fan control
Fan speed manual
• • • • Fan speed [Hi] [Me] [Lo] set by remote controller.
• • • • However, when operation start, or during operation, fan speed control is limited to due to prevent a cold draft, for example, when
heating operation start.
• • • • (K10 = Indoor heat exchanger temperature, depend on indoor type)
26