Terminations; Combustion Air; Exhaust; Concentric Venting Kit - Napoleon 9700 B series Installation And Operating Instructions Manual

Two stage high efficiency (condensing) forced air gas furnace
Hide thumbs Also See for 9700 B series:
Table of Contents

Advertisement

10.0

TERMINATIONS

10.1 COMBUSTION AIR

HORIZONTAL - The combustion air termination is
made up of a medium or long sweep 90° elbow pointing
downward to prevent rain from readily entering the
combustion air intake piping.
If the required clearance to grade cannot be obtained
with the "straight through" confi guration, the combustion
air intake pipe may be "periscoped" up to 24" (610mm) to
gain extra height (Figure 9)
VERTICAL - The combustion air termination is made up
of a pair of medium or long sweep 90° elbow pointing
downward to prevent rain from entering the combustion
air intake piping.
The combustion air inlet must be located a minimum of
12" (305mm) above grade, and 12" (305mm) below the
exhaust outlet. (Figure 11)

10.2 EXHAUST

HORIZONTAL - The exhaust termination is normally a 45° elbow or a medium or long sweep 90° elbow
pointing within 45° of the downward position, away from the combustion air intake terminal.
If the required clearance to grade cannot be obtained with the "straight through" confi guration, the exhaust pipe
may be "periscoped" up to 24" (610mm) to gain extra height. (Figure 9) In this case, the fl ue gases may be
expelled horizontally. Use the same size pipe as the interior run and count the fi ttings and length as part of the
total vent length.
If winter prevailing wind conditions are variable and likely to occasionally blow fl ue gases back in on the
combustion air intake, the exhaust termination may be raised 18-24" (457mm x 610mm) above the combustion
air intake terminal to take advantage of the natural buoyancy of the fl ue gases to help prevent re-circulation of
the exhaust. (Figure 9)
VERTICAL - No termination fi tting is required if venting vertically through a roof.
The end of the exhaust pipe must be 12" (305mm) higher than the entrance of
the combustion air intake terminal. (Figure 11)
The exhaust pipe extending through the roof must extend a minimum of 18"
(457mm) above any obstruction within an 18" (457mm) horizontal distance.
Insulate all venting that extends 24" (610mm) or more to the outside.

10.3 CONCENTRIC VENTING KIT

Concentric venting terminal kits may be used for this series furnace. They provide a means of obtaining
combustion air and exhausting products of combustion utilizing a single penetration through the exterior wall.
This can be useful when there is limited wall space available. Kits are available in:
• 2" Reference kit #196005 (use with model inputs of 30, 40, 60 and 80) Wolf Steel kit W370-0019
• 3" Reference kit #196006 (use with model inputs of 80, 100 and 120) Wolf Steel kit W370-0020
• Terminals are made by IPEX Inc. See installation instructions for details.
If venting with 1½" vent material, and a concentric vent kit is necessary, a increase coupling may be used to
connect to the 2" concentric venting kit. Read the instructions supplied with the kit for additional installation
instructions and details. Straight vertical runs should have offset to push condensate against vent walls.

10.4 CONCENTRIC VENT TERMINATION INSTALLATION INSTRUCTIONS

Follow the concentric vent termination manufacturer instructions for installation of the concentric vent
termination kit. These instructions can be found by contacting the furnace manufacture. Furnace
manufacturer contact information is found on the front cover of this installation manual and operating
instructions.

10.5 LOCATION

Avoid locating the terminals where the fl ue gas could become stagnant and allow recirculation into the
combustion air intake.
FIGURE 11 - STANDARD VERTICAL VENTING
DETAIL
12"
(305mm)
MIN.
18"
(457mm)
MIN.
H15.1
NOTE: Always clean out
exhauster collar after instal-
lation. Vent pipe shavings
from initial installation can
cause blockage in the ex-
hauster collar drain.
H15 2
H15.2
H15.3
H15.4
25
IOM
3"
(76mm)
MIN.
12"
(305mm)
MIN.
ROOF TERMINATION
EXHAUST
W415-1243 / A / 03.19.15