4. COOLING CAPACITY
1 - indoor unit in operation
Indoor Unit
SAP – K91AA ( 1)
Outdoor Unit
SAP – CM1821AA
240 V Single phase 50 Hz
RATING CAPACITY
EVAPORATOR
ENT. TEMP. °C
W.B.
15
17
19
21
23
TC :
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
A(or B)
g
2.50 kW
D.B.
20
TC
2.52
CM
0.72
21
SHC
1.71
23
SHC
1.92
25
SHC
2.13
27
SHC
2.34
29
SHC
2.52
31
SHC
2.52
TC
2.70
CM
0.74
21
SHC
1.49
23
SHC
1.70
25
SHC
1.91
27
SHC
2.12
29
SHC
2.33
31
SHC
2.54
TC
2.88
CM
0.77
21
SHC
1.26
23
SHC
1.47
25
SHC
1.68
27
SHC
1.89
29
SHC
2.10
31
SHC
2.31
TC
3.05
CM
0.79
23
SHC
1.24
25
SHC
1.45
27
SHC
1.66
29
SHC
1.87
31
SHC
2.08
TC
3.23
CM
0.80
25
SHC
1.21
27
SHC
1.42
29
SHC
1.63
31
SHC
1.84
Total Cooling Capacity (kW)
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
CONDENSER
OUTDOOR AMBIENT TEMP. °C
25
30
2.41
2.30
0.78
0.84
1.65
1.59
1.86
1.80
2.07
2.01
2.28
2.22
2.41
2.30
2.41
2.30
2.59
2.47
0.80
0.86
1.43
1.38
1.64
1.59
1.85
1.80
2.06
2.01
2.27
2.22
2.48
2.43
2.75
2.63
# 2.50
0.83
0.89
1.21
1.15
1.42
1.36
1.63
1.57
1.84
1.78
2.05
1.99
2.26
2.20
2.92
2.78
0.85
0.91
1.19
1.13
1.40
1.34
1.61
1.55
1.82
1.76
2.03
1.97
3.09
2.95
0.87
0.93
1.16
1.10
1.37
1.31
1.58
1.52
1.79
1.73
8
35
40
43
2.19
2.06
1.89
0.90
0.97
1.04
1.54
1.47
1.40
1.75
1.68
1.61
1.96
1.89
1.82
2.17
2.06
1.89
2.19
2.06
1.89
2.19
2.06
1.89
2.35
2.21
2.03
0.92
1.00
1.07
1.32
1.26
1.18
1.53
1.47
1.39
1.74
1.68
1.60
1.95
1.89
1.81
2.16
2.10
2.02
2.35
2.21
2.03
2.35
2.16
0.95
1.03
1.10
1.10
1.03
0.96
1.31
1.24
1.17
1.52
1.45
1.38
1.73
1.66
1.59
1.94
1.87
1.80
2.15
2.08
2.01
2.65
2.49
2.29
0.98
1.06
1.13
1.08
1.02
0.94
1.29
1.23
1.15
1.50
1.44
1.36
1.71
1.65
1.57
1.92
1.86
1.78
2.78
2.60
2.42
1.00
1.08
1.16
1.04
0.98
0.91
1.25
1.19
1.12
1.46
1.40
1.33
1.67
1.61
1.54
NOTE
A : SAP–K91AA
B : SAP–K91AA