Viessmann Vitodens 200-W WB2B 80 Start-Up/Service Instructions page 62

Wall-mounted, natural gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W WB2B 80:

Advertisement

Troubleshooting
Corrective Action
A
Fig. 23
A
Fig. 24
62
(continued)
Check fixed high limit
Check the fixed high limit, if the burner control cannot be reset after a fault
shutdown, although the boiler water temp. is below approx. 75°C / 167°F:
Check fuse
F1
Check fuses in the power/pump module
1. Remove cables from the fixed high
limit A.
2. Check the continuity of the fixed
high limit with a multimeter.
3. Remove and replace a defective
fixed high limit.
4. After starting up the boiler, press "
RESET" on the boiler control.
1. Switch OFF the power.
2. Release side latches and
pivot the control unit down.
3. Remove cover A.
4. Check fuse F1 (see wiring diagram).
1. Switch OFF the power.
2. Open power/pump module and
check fuses F1 and F2
(see wiring diagram).