Download Print this page

Viessmann Vitodens 200-W WB2B 80 Start-Up/Service Instructions page 25

Wall-mounted, natural gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W WB2B 80:

Advertisement

Steps
(continued)
I
S
nitial start-up
ervice
26. Clock natural gas meter
Clock natural gas meter to verify input.
Ensure all other gas equipment
1.
served by the meter is turned off
during timing of gas input to the
Vitodens 200-W, WB2B boiler.
2.Measure the time in seconds it takes
for the boiler to use 10 ft.
Divide 3600 x 10 by the number of
seconds and you get the number of
3
ft.
of gas used per hour. Multiply
this number by the heating value of
the gas to obtain Btu per hour input.
Initial Start-up and Service
For example:
A Vitodens 200-W, WB2B 105 boiler
(370 000 Btu/h input) requires 97
sec. to use 10 ft.
After contacting the local utility, you
will find the heating value is
3
of gas.
1000 Btu per ft.
Therefore,
3,600 sec./h x 10 revolutions
36,000/97 x 1000
input. The boiler input is correct.
Burner input formulas
(for low altitude only):
INPUT=(3600
t=TIME (sec.) for 1 ft.
INPUT=(3600 x .01 x 1000 x
÷
35.31)
T where
T = TIME (sec.) for .01 m
gas
IMPORTANT
A boiler underfired by 5% is
acceptable. Do not overfire the boiler.
CAUTION
Always contact your gas utility to
obtain the correct heating value before
clocking the meter.
3
of natural gas.
3
.
370 000 Btu/h
÷
t) x 1000 where
3
3
natural
25

Advertisement

loading

This manual is also suitable for:

Vitodens 200-w wb2b 105