Viessmann Vitodens 200-W WB2B 80 Start-Up/Service Instructions page 38

Wall-mounted, natural gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W WB2B 80:

Advertisement

Coding
Coding Level 1
(continued)
Overview of coding addresses
Coding (factory default setting)
System design
00 :1
System type 1, 2:
1 heating circuit without mixing valve,
without DHW heating
Maximum boiler water temperature
06:...
Maximum boiler water temperature limit
(defaulted by the boiler coding card)
Bleeding air/Filling
2F:0
2F:0
Air bleed program/fill program disabled
Air bleed program/fill program disabled
Participant no.
77:1
LON participant number
DHW priority (heating circuit without mixing valve, A1)
A2:2
DHW priority to heating circuit pump
DHW priority (heating circuit with mixing valve, M2)
A2:2
DHW priority applicable to heating circuit
pump and mixing valve
pump and mixing valve
38
Coding addresses not discussed in this section must not be changed. See page 37
for information of how to access the coding addresses in coding level 1.
Possible change
00 :2
00 :3
00 :4
00 :5
00 :6
06:20
to
06:127
2F:1
2F:2
77:2
to
77:99
A2:0
A2:0
A2:1
A2:3
to
A2:15
System type 1, 2:
1 heating circuit without a mixing valve, with
DHW heating
System type 3, 6, 8:
1 heating circuit with mixing valve,
without DHW heating
System type 3, 6, 8:
1 heating circuit with mixing valve,
with DHW heating
System type 4, 5, 7:
1 heating circuit without mixing valve and 1
heating circuit with mixing valve,
without DHW heating
System type 4, 5, 7:
1 heating circuit without mixing valve; 1 htg.
circuit with mixing valve, with DHW heating
Maximum limit of the boiler
water temperature within the ranges defaulted
by the boiler coding card
Air bleed program enabled
Fill program enabled
LON participant number, adjustable from 1 to
99:
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 200-H, HK1S/HK1M
99 = Vitocom
Note:
Allocate each number only once.
Without DHW priority to heating circuit pump
Without DHW priority applicable to heating
circuit pump and mixing valve
DHW priority only applicable to mixing valve
Reduced priority applied to mixing valve (the
heating circuit receives a reduced amount of
energy)