GE Fuji Electric AF-300 MICRO-SAVER II Instructions Manual page 27

1/4 - 5 horsepower
Hide thumbs Also See for Fuji Electric AF-300 MICRO-SAVER II:
Table of Contents

Advertisement

LED
Data
Display
Setting
Description
*F_35
0.00
GAIN FOR FREQUENCY SETTING SIGNAL
to
This sets the size (gradient) of the output frequency
250
corresponding to the analog frequency setting as a
percentage of the maximum frequency.
[Example: for 70% gain]
*The gain setting is only active when F_01 = 1
Example:
If the bias frequency function (F_34) and the gain for
frequency setting signal function (F_35) are used together,
the gain for frequency setting signal has priority, and the
bias is applied to the frequency with gain already applied.
The bias frequency f
bias
this time can be calculated by the following formulas.
f
– f
1
2
f
= f
bias
1
V
V
1 –
2
1000 x (f
Gain =
100 x (V
– V
1
Example:
If the analog frequency setting voltage is 1 to 5Vdc
and the output frequency is weighted to 0 to 100% then:
(V
, f
) = ( 1, 0) , (V2, f2) = ( 5,100), so that
1
1
[V]
[%]
f
= –25% and gain = 200%
bias
6-14
Factory
Customer
Setting
Setting
100.0%
[Example for 200% gain]
and setting frequency gain at
x V
1
– f
)
1
2
) + f
x V
– f
x V
2
1
2
2
1
[V]
[%]
LED
Data
Display
Setting
Description
*F_36
0 to 400
HIGH FREQUENCY LIMITER
*F_37
0 to 400
LOW FREQUENCY LIMITER
The high and low limits for the output frequency can be
set within a range of 0 to 400Hz in stages of 1Hz.
NOTE:
If the high and low limit settings are reversed, the high
limit has priority and the low limit is ignored.
*F_38
0 to 10
MOTOR CHARACTERISTICS
This adjusts the output current in cases where there is
an irregularity such as current fluctuation. If a current
fluctuation occurs, adjust the setting value while
referring to the tables below.
Number of
Higher
Motor Poles
Setting
0
F_39
DATA INITIALIZATION
This resets all Function Codes to factory settings.
0:
Inactive (manual setting)
1:
Initial values (Initialization with factory defaults)
[Operation Procedure]
When 0 is being displayed, press the STOP +
keys simultaneously to change the display to 1.
In this condition, press the
all data to the factory default settings. The display
will then automatically switch to show the frequency
setting for STOP mode.
Factory
Customer
Setting
Setting
70 Hz
0 Hz
5
4
Lower
Load High
Low
10
Setting
0
10
0
FUNC
key to reset
DATA
6-15