Download Print this page

Refrigerating Cycle Block Diagrams - Samsung ACH2400C Service Manual

Cassette type air conditioner

Advertisement

5. Refrigerating Cycle Block Diagram
5-1 Model : ACH2800C
Indoor Unit
Capallary Tube
Heat
Exchanger
(Evaporator)
Cooling
Heating
Gas leak check point
*Amount of refilling per extension length of 1m;
When extending the pipe length by more than 5m, 40gr(50gr: Outdoor Unit is higher than Indoor Unit) of R-22
refrigerant should be refilled per extension length of 1m.
*Allowable pipe length : Max. 30m
*Allowable drop distance : Max. 15m
3-Way Valve
Capallary Tube
Gas Side
3-Way Valve
Outdoor Unit
Check Valve
Capillary Tube
Heat
Exchanger
(Condenser)
Reservior
4-Way Valve
Muffler
Accumulator
Compressor
High Pressure switch
51

Hide quick links:

Advertisement

loading