Setting heating set point, St2 (only for units supplied with internal heater):
1. Press "SET" twice slowly and display should show St2 and then the pre-set value of St2. (default: +5°C /
+41°F)
2. Reach the desired value by using ▲ or ▼.
3. Press "SET" again to save the new value of St2.
​ S etting temperature units (°C / °F), low temperature alarm and high temperature alarm:
1. Press "PRG" button for 5 seconds to reach the modifiable parameter list.
2. Use ▲ or ▼ to reach the desired parameter:
C18 for temperature unit of measure
°C = 0
°F = 1
P25 for low temperature alarm threshold (default -10°C / +14°F)
P26 for high temperature alarm threshold (default +55°C / +131°F)
3. Press "SET" on the desired parameter to display the current value.
4. Use ▲ or ▼ to reach the desired value.
5. Pressing "SET" temporarily saves the new value and returns to the parameters list.
6. Repeat steps 2-5 to set other parameters.
7. Press "PRG" for 5 seconds to permanently save the new values.
Set Point
Cooling
Heating (for units with heater) St2
Low Temperature Alarm
High Temperature Alarm
Test function
Different test functions can be used depending on the combination of keys pressed. Such tests run for the
duration of 4 minutes.
"SET+▲" tests Compressor and Ambient Blower relays.
"SET+▼" tests Alarms and Heater relays
Version No. 1-18 - 12.02.2022
Paramter
Default
St1
35°C / 95°F 20°C - 50°C / 68 -122°F
5°C / 41°F
P25
-10°C / 14°F -50°C - P26 / -58°F - P26
P26
55°C / 131°F P25 - 150°C / P25 - 302°F
Doc. No. 9957202182SG
Range
-20°C - 20°C /-4°F - 68°F