Backwash Supply iii. Waste Line vii. Media Installation 2. Documentation Media MSDS Installation Check List iii. Request for Startup Startup Data Sheet Filter Log Sheet AmeriWater Warranty 3. Operation Seasonal Startup Seasonal Shutdown iii. Freeze Protection Sequence of Operation 6/07...
Page 3
4. Maintenance Maintenance Schedule Control Functions iii. Media (Level & Condition) Pump Service Troubleshooting Guide 5. Drawings 6. System Component Cut Sheets 6/07...
Page 4
Systems Series CW This Installation, Operation, and Maintenance manual contains instructions for the AmeriWater filter series CW. Check the model number on your filter system (located on the inside of control enclosure door). If CW is not present in model number - Do Not Proceed.
AmeriWater 800.535.5585. b) Remove top of crate then break down sides as necessary to remove contents. Report any damage immediately to AmeriWater 800.535.5585l c) Unpack filter system as close as possible to installation location. d) Flange gaskets, bolts, and pipe stand hangers (if applicable) are contained in cardboard boxes packed in crate(s).
1.4 Filter System Assembly Placing, Arranging, and Leveling Vessel(s) Skid mounted systems: a) Place system skid in desired location and level skid. NOTE: If system was shipped assembled, the pipe assembly may be loose at flanges to avoid flex damage. Some systems will be shipped broken down to avoid damage from flexing. b) Arrange vessels with valves front.
Assembling Manifolds NOTE: Flange bolts, and gaskets are packed in separate cardboard box contained in filter shipping crate. a) Align upper and lower manifolds with vessels. Install flange gaskets and bolt manifold flanges to vessel(s). Do not tighten flange bolts at this time. Minor adjustments in vessel alignment may be necessary at this time.
Output #11 will be fused, (if applicable) to change timed backwash from 24 hours to 7 days. Timed backwash should be changed only for systems operating on a closed loop and only after consultation with AmeriWater. NOTE: Changes to these options without instructions from AmeriWater may void the filter warranty. 6/07...
Connecting pipe should be of materials compatible in construction to filter manifold. Dielectric fittings are highly recommended if dissimilar metals are used. For pipe runs exceeding 20 feet from filter system consult AmeriWater for pipe size recommendations. The companion full-face flange to the suction side of the filter pump is to be provided by end- user or contractor.
Ball Type or Spring Type Checks Are Not Acceptable. For drainpipe runs exceeding 20 feet or an 8-foot lift from filter system, consult AmeriWater for pipe size recommendations. Connect properly sized drain line to filter backwash drain.
Page 11
AmeriWater if media loss is suspected. All loses must be verified by authorized factory representative. NOTE: For multi-vessel systems be sure that each vessel has the same number of media containers per layer and same number of layers. b) b. Remove top filter vessel closure.
2 Documentation THE PARRY COMPANY 2.1 Media MSDS 33630 Old US Route 35 Chillicothe, OH 45601 Ph: 740-884-4893 Fax: 740-884-4892 Material Safety Data Sheet I. PRODUCTION IDENTIFICATION Trade Name as Labeled: Silica Gravel; 6x12 Mesh Chemical Name and Formula: Silica, in the form of quartz; SiO2 II.
Page 13
Silicosis may be progressive; it may lead to disability and death. Cancer: Crystalline silica (quartz) inhaled from occupational sources is classified as carcinogenic to humans. Autoimmune Diseases: There are some studies that show excess numbers of cases of scleroderma and other connective tissue disorders in workers exposed to respirable crystalline silica.
Page 14
VII. HANDLING AND STORAGE Ventilation and Engineering Controls: Local mechanical to reduce respirable silica to below safe levels. Respiratory Protection (Type): Use NIOSH approved equipment. Positive pressure supplied air-type recommended. Appropriate respiratory protection for respirable particulates is based on consideration of air borne workplace concentrations and duration of exposure arising from the intended end use.
Page 15
Exposure Guidelines: Component Percent OSHA OSHA ACGIH ACGIH NIOSH NIOSH Unit (TWA) (STEL) (TWA) (STEL) (TWA) (STEL) (by wt.) Crystalline Silica 14808 99.0- % SiO2 + 2 None None None Mg/m³ (Quartz) -60-7 99.9 IX. PHYSICAL AND CHEMICAL PROPERTIES Vapor Density: Not applicable Melting Point: 1710°C Specific Gravity: 2.65 Boiling Point: 2230°C...
Page 16
cristobalite from occupational sources is carcinogenic to humans (Group 1).” The IARC evaluation noted that “carcinogenicity was not detected in all industrial circumstances studies. Carcinogenicity may be dependent on inherent characteristics of the crystalline silica or on external factors affecting its biological activity or distribution of it polymorphs.”...
Page 17
General: The packaging and material may be land filled; however, material should be covered to minimize generation of airborne dust. RCRA: Crystalline silica (quartz) is not classified as a hazardous waste under the Resource Conservation and Recovery Act, or its regulations, 40 CFR §261 et. seq. The above applies to materials as sold by Fairmount Minerals, LTD.
Page 18
*Chronic exposure to respirable size silica will result in silicosis. **Comply with special OSHA respiratory protection if sandblasting. XVII. ACRONYM LIST CAS: Chemical Abstract System ACGIH: American Conference of Governmental Industrial Hygienists OSHA: Occupational Safety and Health Administration PEL: Permissible Exposure Limit TLV: Threshold Limit Value NIOSH: National Institute of Occupational Safety and Health NTP: National Toxicology Program...
2.2 Installation Check List ______ All flange bolts and unions tightened. ______ Media installed. (Sec 1.7) ______ Vessel caps installed and secured. ______ All recommended components installed per Typical Installation Sketch. (Drawing CWT) ______ Filter effluent (return) line connected to cooling system at point where pressure is equal to or lower than filter influent (supply) line.
2 Weeks advance notice is required for startup. AmeriWater Fax: 937.461.1988 Please have a factory authorized technician contact me to arrange startup for the AmeriWater Sand Filter System. System location: ___________________________________________ Note: All items listed below must be complete before startup personnel arrive. Should installation not be complete, additional charges may be incurred, including but not limited to, additional labor hours, travel expenses, and materials provided for startup.
AmeriWater’s obligation under this warranty is limited to repair or replacement of any part or parts found to be defective. AmeriWater shall not be required to incur expenses for labor outside of the place(s) of business of AmeriWater, nor travel expenses to fulfill its obligations hereunder.
Manually remove any debris from top of sand. e) Level of sand in the filter vessel should be approximately 7.5" – 8.5” from bottom of filter inlet. If media level is below normal or appears other than loose sand, contact AmeriWater 800.855.5535.
PSI). e. Check voltage and amperage on pump motor leads. Current /amp draw should not exceed rating on motor nameplate. f. Check system for unusual noise or vibration. Contact AmeriWater 800.535.5585 if any unusual conditions are noted. 3.2 Seasonal Shutdown...
SEQUENCE OF OPERATION This section describes the operation of standard High Efficiency Filter Systems as they are shipped from the factory. It is intended to be an aid to understanding the general operation of the unit for the equipment operator and should not be considered a technical reference. Modes of operation There are two modes of operation for the CW Series.
Page 27
The backwash timer will automatically initiate a backwash at pre-determined intervals. The standard interval is every 24 hours. This can be changed to a 7-day interval by installing a fuse in the fuse holder labeled 7 for closed loop systems. Consult your AmeriWater representative for information. Setting the automatic timer The 24 hour or 7 day automatic backwash timer can be reset to zero by pressing and releasing the “manual backwash”...
Page 28
(Step 1). This is accomplished by installing a fuse at the appropriate location in the control box labeled P. Consult your AmeriWater representative for information. To disable (turn off) the pump for maintenance, etc., rotate the pump selector switch on the control box to the “off”...
Page 29
Electrical Component Description 1) Power Disconnect Switch – Main power supply to filter ON/OFF switch. 2) Pump On Indicator Light – Illuminated when filter pump is ON. 3) System Power On Indicator Light – Illuminated when disconnect switch is in the on position and power is to the filter.
Page 30
16) Terminal 20 & 21 – “Filter Lockout Output” is an output (dry contact) to first filter system “Backwash Interlock Input” terminals 1 &17 to prevent system from backwashing at the same time. 17) Terminal 2 & 24 – Wet Contact – 120V output when filter is in backwash. Deactivated when filter is in service.
Page 32
4 Maintenance 4.1 Maintenance Schedule AmeriWater High Efficiency Filter Systems are designed for low maintenance. The following maintenance procedures are minimum frequency and will help to ensure continued trouble free operation. Refer to component cut sheets for maintenance instructions specific to your equipment.
Page 33
a.3 Media (level & condition) a) Backwash filter (De-energize control panel before last vessel is finished backwashing). b) Isolate filter system from all water sources. c) Open bottom filter drain (Ensure that pressure drops to zero). d) Remove vessel cap and gasket. e) Drain water to top of media then close drain.
Page 34
System Piping Unusually Warm Filter Discharge to Dead Head Open all valves Check automatic valve functions Check for proper system installation Media Plugged See media failure If recommended remedy fails, contact AmeriWater 800.585.5535 for further information. 6/07...
Page 36
CP = Control Panel Enclosure with Labeled Components...
Page 39
TBIO = Input/output strips on Terminal block labeled to indicate connection points...
Page 40
CPIO = Input/output strips on PLC labeled to indicate connection points...
Page 43
ML = Media Label MEDIA LAYER 1 (LOAD FIRST) GRAVEL ½ x ¼ Caution: Product contains silica. See MSDS for proper handling and safety precautions. __________ OF __________ The Media Layer number on the Media Label corresponds to the order in which it is to be loaded (for example, Media Layer 1 is loaded first, Media Layer 2 second, etc.).
SAFETY INSTRUCTIONS limit maximum voltage drop to 10% of nameplate voltage at motor terminals, or motor life and pump TO AVOID SERIOUS OR FATAL PERSONAL performance will be lowered. INJURY OR MAJOR PROPERTY DAMAGE, READ 1.4. Always use horsepower-rated switches, contactor and AND FOLLOW ALL SAFETY INSTRUCTIONS IN starters.
3.2. Suction pipe must be at least as large as the suction 5. ROTATION connection of the pump. Smaller size will degrade 5.1. Correct rotation is right-hand (clockwise when performance. viewed from the motor end). Switch power on and 3.3. If larger pipe is required, an eccentric pipe reducer off quickly.
the two parts. The mechanical seal rotary unit 10. TROUBLESHOOTING CHART (383) should come off the shaft with the seal housing. MOTOR NOT RUNNING (See causes 1 through 6) 8.4.6. Push out the mechanical seal stationary seat from the motor side of the seal housing. LITTLE OR NO LIQUID DELIVERED (See causes 7 through 17) 9.
MECHANICAL SEAL APPLICATION CHART COMPONENTS LIST Casing Item No. Description Materials Rotary Stationary Elastomer Metal Parts Part No. O-ring Casing Cast iron Ceramic BUNA 18-8SS 10K10 BUNA Impeller AISI 316L SS Carbon EPR 10K18 Motor adapter Steel Viton 10K55 Viton 123 Deflector BUNA-N...
Page 51
COMMERCIAL WARRANTY For goods sold to commercial buyers, Seller warrants the goods sold to Buyer hereunder (with the exception of membranes, seals, gaskets, elastomer materials, coatings and other “wear parts” or consumables all of which are not warranted except as otherwise provided in the quotation or sales form) will be (i) be built in accordance with the specifications referred to in the quotation or sales form, if such specifications are expressly made a part of this Agreement, and (ii) free from defects in material and workmanship for a period of one (1) year from the date of installation or twelve (12) months from the date of shipment (which date of shipment shall not be greater than eighteen (18) months after receipt of notice that the goods...