CONDUIT BOX REMOVAL
1. Note the location and markings (re-mark
as required) and remove connections from
voltage regulator (Figure 6-4), capacitor
(Figure 6-5), and any other conduit box
mounted controls.
Figure 6-4
Figure 6-5
2. On generators equipped with bus bars,
mark all connections and disassemble main
stator (power) leads from the generator side
of the bus bars.
3. Remove bolts holding conduit box in
place. (Figure 6-6.)
4. Remove conduit box. (Figure 6-7).
29
Figure 6-6
Figure 6-7