15.5.19. F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the outdoor pipe
temperature sensor.
Malfunction Caused
• Air short circuit at outdoor unit.
• Dust accumulation on the outdoor unit heat exchanger.
• 2/3 way valve closed.
• Faulty outdoor unit fan motor.
• Excessive refrigerant.
• Clogged expansion valve or strainer.
• Faulty outdoor pipe temperature sensor.
• Faulty outdoor unit PCB.
Troubleshooting