ABB Relion 670 Series Product Manual page 13

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Busbar protection REB670
Version 2.2
QA1
QA1
QA1
BI1
BI1
BI1
QA2
QA2
QA2
BI2
BI2
BI2
BI3
BI3
BI3
QA3
QA3
QA3
IEC11000240 V1 EN-US
Figure 8.
Example of one-and-a-half breaker station
Table 7. Typical solutions for one-and-half circuit breaker stations when CBF for middle breaker is not required
Version of REB670 pre-configured IED
3PH; 2-zones, 4-bays BBP (A20)
3PH; 2-zones, 8-bays BBP (A31)
1Ph; 2-zones, 12-bays BBP (B20)
1Ph; 2-zones, 12-bays BBP (B21)
1Ph; 2-zones, 24-bays BBP (B31)
QA1
QA2
QA1
QA2
BI1
BI2
BI1
BI2
IEC06000018 V1 EN-US
Figure 9.
Example of double bus-double breaker station
Table 8. Typical solutions for double circuit breaker busbar arrangement
Version of REB670 pre-configured IED
3PH; 2-zones, 4-bays BBP (A20)
3PH; 2-zones, 8-bays BBP (A31)
1Ph; 2-zones, 12-bays BBP (B20)
1Ph; 2-zones, 12-bays BBP (B21)
1Ph; 2-zones, 24-bays BBP (B31)
Hitachi Power Grids
QA1
QA1
BI1
BI1
QA2
QA2
BI2
BI2
BI3
BI3
QA3
QA3
Number of diameters in the station
2/4
4/8
6/12
6/12
12/24
QA1
QA2
QA1
QA2
BI1
BI2
BI1
BI2
Numbers of feeders per station
4
4/8
6/12
6/12
12/24
© 2017 - 2021 Hitachi Power Grids. All rights reserved
ZA
ZB
IEC11000240-1-en.vsd
ZA
ZB
QA1
QA2
BI1
BI2
xx06000018.vsd
1MRK 505 373-BEN P
Number of REB670 IEDs required for the
scheme
1/2
1/2
3/6
3/6
3/6
Number of REB670 IEDs required for the
scheme
2
1/2
3/6
3/6
3/6
13