INSTRUCTION SHEET
HG1P Series
Confirm that the delivered product is what you have ordered. Read this instruction sheet to make sure
of correct operation. Make sure that the instruction sheet is kept by the end user.
SAFETY PRECAUTIONS
In this instruction sheet, safety precautions are categorized in order of importance from Warning and Caution:
Warning notices are used to emphasize that improper operation may cause severe personal injury or death.
Caution notices are used where inattention might cause personal injury or damage to equipment.
・When using the HG1P in applications which require high level of safety, add a fail-safe or backup
functionality, and verify an adequate level of safety using the product specifications.
・Turn off the power to the HG1P before installation, removal, wiring, maintenance, and inspection of the HG1P.
Failure to turn power off may cause electrical shock or fire hazard.
・Special expertise is required to install, wire, configure, and operate the HG1P. People without such expertise
must not use the HG1P.
・The HG1P uses an LCD (liquid crystal display) as a display device. The liquid inside the LCD is harmful to the
skin. If the LCD is broken and the liquid attaches to your skin or clothes, wash the liquid off using soap, and
consult a doctor immediately.
・An emergency circuit suitable for a system must be configured outside of the HG1P by using the emergency
stop switch mounted on the HG1P unit.
・Do not use touch switches, the function keys and the function switches for an emergency circuit or an
interlocking circuit. If the HG1P fails, equipment connected to the HG1P will no longer be protected, and
serious injury to operators and equipment damage may be caused.
・Create and external circuit between the HG1P and an external device to ensure safety in the event of a loss
of communication.
・Connect the emergency stop switch and the enabling switch on the HG1P to function as either a category 0 or
category 1 stop with IEC/EN60204-1.
・Do not, under any circumstances, hold the enabling switch on the HG1P in position 2 with tape, string, or
deform the rubber cover. The intrinsic function of the enabling switch will be lost, and the enabling switch may
not work in an emergency.
・When using the HG1P, place your finger firmly on the enabling switch.
・Perform regular checks to confirm that the emergency stop switch and enabling switch work properly. It is
extremely dangerous if the enabling switch no longer returns to position 1 due to a foreign object becoming
lodged in the switch because position 2 will be maintained even when you remove your hand.
・Stop using the HG1P if it is accidentally dropped or exposed to significant shocks, check the HG1P for
damage, and confirm that its various functions work safely and correctly.
・Connect the FG wire to grounding resistance of 100 Ω or less. Otherwise there is a risk of electric shock or
mistaken operation.
・When more than one button is pressed at the same time, due to the detection characteristics of an analog
type touch panel, only the center of the pressed area is sensed and the unit assumes that only one button is
pressed. Do not operate the HG1P by pressing more than one button simultaneously because there is a risk
of accident.
・The screen will not be visible if the backlight burns out, the touch panel and the function key will remain
functional. Incorrect touch panel operation or incorrect function key operation will occur when operating the
touch panel when the backlight appears to be off but is actually burnt out. Because such erroneous operation
could result in damage, the touch panel and the function key should not be used after the backlight has
burned out.
・The emergency stop function is disabled when HG1P is removed from the machine. To eliminate the
possibility of accidents caused by operating the disabled emergency stop switch, place the HG1P, removed
from the machine, in a location that is not visible to the operator. Install at least one emergency stop switch
on the machine near the location where the HG1P is connected.
・The HG1P is designed for indoor use only (Not for outdoor use)
・The D-sub connector on the end of the HG1P optional cable is not water- or dust-proof. If protection against
water and dust is required, the user must replace the D-sub connector with a water-proof connector.
・Prevent the HG1P from falling while moving or transporting, otherwise damage or malfunction of the HG1P
will result.
・Use the product within the environmental limits given in the catalog and manual. Use of the product in
hightemperature or high-humidity environments, or in locations where it is exposed to condensation, corrosive
gas or large shock loads can create the risk of electrocution and fire.
・The HG1P is designed for use in pollution degree 2. Use the HG1P in environments of pollution degree 2.
(based on the IEC60664-1 rating)
・Prevent metal fragments or wire chips from dropping inside the HG1P housing. Ingress of such fragments
and chips may cause fire hazard, damage, and malfunction.
・Use a power supply of the rated value. Using a wrong power supply or wiring in reverse polarity may cause
fire hazard and damage.
・Use wire of the HG1P optional cable.
・Make sure of safety before starting and stopping the HG1P. Incorrect operation of the HG1P may cause
mechanical damage or accidents.
・Use the HG1P in a local area network if you download, upload or monitor the project data via the Ethernet
port.
・The touch panel of the HG1P is made of glass, and will break if exposed to excessive shock.
Take due care when handling it.
・Do not push hard or scratch the touch panel and protection sheet with a hard object such as a tool, because
they are damaged easily.
・At temperatures over the rated operating temperature, the clock accuracy is affected. Adjust the clock before
use.
・Do not install the HG1P in areas subjected to strong ultraviolet rays, since ultraviolet rays may impair the
quality of the LCD.
・Do not attempt to disassemble, repair or modify the HG1P. This can create the risk of fire or electrocution.
・When disposing of the HG1P, do so as an industrial waste.
・Do not switch off the power or pull out the USB flash drive while it is being accessed, as this may result in
destruction of the stored data. If the data on the USB flash drive is corrupted, reformat the USB flash drive.
・Install the HG1P according to the instructions. Improper installation may result in, failure, electrical shock, fire
hazard, or malfunction of the HG1P.
・If it is used in a way incompatible with the HG1P original use purpose, the function provided by the HG1P
may be impaired.
1
Packing Content
B-2026(3)
Before installing the HG1P, make sure that the product conform to your order, and that no parts are
missing or damagesd due to accidents during transportation.
Name
Pcs.
HG1P Unit
1
2
Type Number
Communication Interface
Type No.
Serial Interface (RS422 /485)
HG1P-ST32YBFH-B0
Ethernet Interface
HG1P-ST32ZBFH-B0
3
Part Names
191
(2)
(8)
(1)
(9)
(3)
(4)
(5)
(6)
(7)
(12)
(13)
No.
Name
Description
(1)
Mechanical Switch 1
Type No.: AB6E-3BV02PRM (IDEC)
(Emergency Stop Switch)
Contact Rating: 1A/DC30V
(2)
Mechanical Switch 2
Type No.: LB6S-2T1 (IDEC)
(Selector Switch)
Contact Rating: 0.1A/DC30V (resistance load)
(3)
Function Key
12
(4)
Display
TFT color LCD
(5)
Touch Panel
Analog Resistive Film
POWER LED
Green (lit): Normal Operation (Power is on), Not lit: Power is off
(6)
(7)
Connector
Removable 19-pin Round Female Connector
(8)
Mounting Hole For Wall-Mounted Hook
Wall-mounted hook fixing screw mounting part (2)
(9)
Name Plate
Label printed with Part number, Serial Number and Consumption
Current
(10)
Enabling Switch
Type No.: HE6B-M200Y (IDEC)
Contact Rating: 1A/DC30V (resistive), 0.7A/DC30V (pilot duty)
(11)
Hand Strap Mounting Part
-
(12)
USB Port Cover
-
(13)
USB Port Cover Mounting Part
USB port cover fixing screw mounting part (1)
(14)
USB Interface (USB2)
USB2.0 (Host) Connector: Type A
(15)
USB Interface (USB1)
USB2.0 (Device) Connector: Mini-B
4
External Interfaces
・Connector Type
Removable 19-pin Female Connector:CA-19P1N126Y00 (PHOENIX CONTACT)
No.
Name
Function
1
C_NC1
Selector Switch Contact 1 (NC)
C_NO1
Selector Switch Contact 1 (NO)
2
Enabling Switch Contact 1 (COM)
3
B_C1
Enabling Switch Contact 2 (COM)
4
B_C2
B_NO2
Enabling Switch Contact 2 (NO)
5
6
FG
Frame Ground
7
RDA+/TP1+
Receive Data (+)
8
RDB-/TP1-
Receive Data (-)
9
SDB-/TP0-
Send Data (-)
10
A_NC21
Emergency Stop Switch Contact 2 (NC)
11
A_NC22
Emergency Stop Switch Contact 2 (NC)
View of mating surface of the
12
DC24V-
HG1P 24V DC Power Supply (-)
detachable connector
Selector Switch Contact 1 (COM)
13
C_C1
B_NO1
Enabling Switch Contact 1 (NO)
14
15
SG
Communication Signal Ground
16
SDA+/TP0+
Send Data (+)
17
A_NC11
Emergency Stop Switch Contact 1 (NC)
18
A_NC12
Emergency Stop Switch Contact 1 (NC)
19
DC24V+
HG1P 24V DC Power Supply (+)
5
Specifications
・The following specifications are when the HG1P optional cable specified by IDEC is attached.
・ For details, refer to the WindO/I-NV4 User's Manual.
Applicable Standards
Safety Standards
UL61010-1
UL61010-2-201
CSA C22.2 No.61010-1 (c-UL)
CSA C22.2 No.61010-2-201 (c-UL)
EMC Standards *1
IEC / EN 61131-2
FCC *2
Environmental Specifications
Operating Temperature
0 to +45°C
Operating Humidity
10 to 90% RH (no condensation)
-10 to +60°C
Storage Temperature
Storage Humidity
10 to 90% RH (no condensation)
Altitude and Atmospheric Pressure
Up to 2000m (RUN), 750 to 1060hPa
Unit: mm
Pollution Degree
2
Corrosion Immunity
Free from corrosive gases
Electrical Specifications
Rated Voltage
24V DC
Power Consumption
3W maximum *3
Power Voltage Range
20.4 to 28.8V DC
Allowable Momentary Power Interruption
10ms maximum
Inrush Current
20A maximum
Dielectric Withstand Voltage
AC500V, 10mA, 1 minute (between power and earth terminals)
Construction Specifications
Vibration
5 to 8.4Hz amplitude 3.5mm, 8.4 to 150Hz acceleration 9.8m/s²
1 octave 10 minutes 10 times on each of three mutually
perpendicular axes (100 minutes) (IE61131-2)
Shock
147m/s², 11ms
(5 shocks on each of three mutually perpendicular axes) (IEC61131-2)
(10)
Dropping
1.5m, 6 directions, 1 time
(11)
HG1P Optional Cable: 100 times
Connector Insertion Life
(14) (15)
USB1: 5000 times, USB2: 1500 times
Communication Specifications
Serial Interface
Communication Speed
187500, 115200, 57600, 38400, 19200, 9600, 4800, 2400, 1200 bps
(RS422/485)
20m maximum
Communication Distance
Synchronization
Asynchronous
Ethernet
Interface Specification
IEEE802.3i, IEEE802.3u
Interface
10Mbps, 10/100Mbps
Baud Rate
*1 When selecting the connection speed of the Ethernet interface of 10/100 Mbps and using HG1P as the
EMC Standard Approved Products, attach 2 ferrite cores near the connector of HG1P side on the HG1P
optional cable.
And, fasten the ferrite cores to the cable with the clamp bands.
Connector for HG1P
*2 When not using USB Interface (USB2): 2W maximum
*3 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the user will be required to correct
the interference at his own expense.
Supplier's Declaration of Conformity 47 CFR § 2.1077 Compliance Information
Unique Identifier:
HG1P-ST32YBFH-B0, HG1P-ST32ZBFH-B0
Responsible Party – U.S. Contact Information
IDEC Corporation
1175 Elko Drive, Sunnyvale, CA 94089-2209, USA
Tel: +1-408-747-0550 opencontact@idec.com
FCC Compliance Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
6
Installation
6.1 Operating Environment
・ For designed performance and safety of the HG1P, do not install the HG1P in the following
environments:
- Where dust, briny air, or iron particles exist.
- Where oil or chemical splashes for long time.
- Where oil mist is filled.
- Where direct sunlight falls on the HG1P.
- Where strong ultraviolet rays fall on the HG1P.
- Where corrosive or combustible gasses exist.
- Where shocks or vibrations are transmitted.
- Where condensation occurs due to rapid temperature change.
- Where high-voltage or arc-generating equipment (electromagnetic contactors or circuit protectors)
exists in the vicinity.
- Near devices that generate a lot of heat. Such as a boiler.
・Use the wall-mounted hook (optional item) for wall mounting.
6.2 Installation
・Attaching the HG1P Optional Cable (HG9Z-XCP13/-XCP15/-XCP17) to the HG1P
・ Make sure to turn off the power to the HG1P before inserting or pulling the cable into or out of the
connector.
・ After locking the connector, gently tug on the cable to make sure that the connector does not come off.
・ Do not apply an excessive tensile load to the cable, otherwise damage of the connector will result.
(1)
Mating Positioning Mark
(2)
"open"
Logo
(1) Turn the connector cap.
(2) Pull off the connector cap where the resistance lessens.
(3) Turn the connector at the end of the HG1P optional cable to align the "open" text with the logo.
(4) Align the connector at the end of the HG1P optional cable with the mating positioning mark, and then
push it straight on until the rubber (black) is completely covered.
(5) Turn the shaded portion of the connector clockwise 90°.
The connector will stop turning at 90°. Do not try to turn it past 90°.
・Removing and Installing the USB Port Cover
・ When attaching the cover, tighten the screw to the recommended tightening torque (0.6 N·m).
・ When installing the HG1P, make sure that the gasket is not twisted. Because any twistitng in the
gasket will impair the waterproof characteristics.
<Removing the USB Port Cover>
USB Port Cover
Unscrew the USB port cover fixing screw with a Phillips
screwdriver, and then pull the USB port cover outward to
open it.
Only one side of the USB port cover opens.
Be careful when opening the USB port cover because the part
that opens may be damaged if excessive force is used.
USB Port Cover
Fixing Screw
Phillips Screwdriver
<Installing the USB Port Cover>
While pressing the USB port cover with your finger, close it
and tighten the USB port cover fixing screw to the
recommend tightening torque while keeping it from lifting up
from the case.
Do not remove the USB port cover fixing screw from the USB
port cover.
Press with your finger
Recommended ferrite core:
E04SR211132 (2 pcs.) manufactured
7
Maintenance and Inspection
by SEIWA ELECTRIC MFG Corporation
Maintain and inspect the HG1P periodically to ensure the best performance.
Clamp Band
Do not disassemble, repair, or modify the HG1P during inspection.
Maintenance and
Description
Inspection Parts
Display
Wipe any stain of the display using a soft cloth slightly dampened with neutral
detergent or alcoholic solvent. Do not use solvents such as thinner, ammonia, strong
acid, and strong alkaline.
Connector
Check the connectors to make sure of incomplete insertion, or disconnected lines.
USB Port Cover
Make sure of no loose screws, or no twisted gasket.
Wall-Mounted Hook
Make sure of no loose screws.
Backlight
The HG1P's backlight cannot be replaced.
Touch Panel
A gap may be caused in the operation accuracy of the touch panel by the secular
distortion, etc. Readjust the touch panel according to the following procedure when
there is a gap in the operation of the touch panel.
8
Options
Name
Type Number
Maintenance Cable
HG9Z-XCM42
HG1P Optional Cable
HG9Z-XCP1*
(*: Cable Length)
HG1P Debug Cable
HG9Z-PX12
Hand Strap
HG9Z-PS4
Wall-Mounted Hook
HG9Z-PK3
Manufacturer: IDEC CORP.
2-6-64 Nishimiyahara Yodogawa-Ku, Osaka 532-0004, Japan
EU Authorized Representative: APEM SAS
55, Avenue Edouard Herriot BP1, 82303 Caussade Cedex, France
UK Authorized Representative:APEM COMPONENTS LIMITED
Drakes Drive, Long Crendon, Buckinghamshire, HP18 9BA, UK
Rubber
(5)
(4)
(Black)
(3)
<Before locking the connector>
<After locking the connector>
Description
USB cable to connect to a computer
Length: 2m
<Connector>
HG1P: USB Mini-B
Computer: USB Type-A
Communication Mode: RS422/485 or Ethernet
Length: 3m, 5m, 7m
<Connector>
HG1P: CA-19S1N128007S
Host: D-sub 25-pin Male Connector
Length: 2m
<Connector>
HG1P: CA-19S1N128007S
Host: Twisted Wire
Wrist strap
1 pc/pack
Hook attached to the rear of the case
1 pc/pack, Includes two installation screw