Chiller Maintenance; Condenser; Pump Motor; Circulation System - Cornelius CH Series Operator And Installation Manual

Hide thumbs Also See for CH Series:
Table of Contents

Advertisement

CH Series Chiller Operator's & Installation Manual
!
WARNING:
Disconnect power to the unit before servicing. Follow all lock out/tag out procedures established by the user. Verify all
power is off to the unit before performing any work.
Failure to comply could result in serious injury, death or damage to the equipment.
C
ONDENSER
On air-cooled chillers, the CONDENSER FINS should be cleaned by blowing compressed air through the condenser
from the fan side. Dirt and debris accumulate on the condenser fins over time and this build up can severely reduce
the performance of the chiller. Cleaning of the CONDENSER COIL FINS should be done approximately every three
months, depending upon cleanliness of your application.
P
M
UMP
OTOR
The PUMP MOTOR should be lubricated with thirty drops of SAE 20 oil once a year.
C
S
IRCULATION
YSTEM
The CIRCULATION SYSTEM should be drained and flushed periodically to avoid build up and a possible flow
restriction caused by contaminants.
Publication Number: 620914801

CHILLER MAINTENANCE

- 8 -