Application Table - Indirect Hot Water Tank Sizing - UTICA BOILERS MAHF-100 Manual

Condensing gas fired boiler
Table of Contents

Advertisement

APPLICATION TABLE - INDIRECT HOT WATER TANK SIZING

Max. First
Hour Rating
Model
Gal/Hr. @
140 F 115 F 140 F
H20I30
176
H2OI40
193
H2OI40L
186
H2OI50
196
H20I60
231
H20I60L
211
H2OI80
241
H2OI115
291
High Output Units 60HO, 80HO, and 115HO
H2OI60HO
353
H2OI80HO
366
H2OI80HOC
386
H2OI15HO
413
H2OI115HOC
423
Extra High Output Units 85XHO and 115XHO
H2OI85XHOC
649
H2OI115XHOC
674
Notes:
176 °F Boiler Supply Water Temperature, AHRI Conditions -50 °F Inlet
Water @ 240 GPH Flow Rate.
HEATING ONLY BOILERS 100, 125, 165
Continuous
Rating
Gal/Hr @
115 F
233
149
206
254
157
218
251
150
215
254
151
231
298
177
244
272
157
218
306
169
234
363
188
260
468
299
414
479
294
407
507
314
435
532
310
429
545
320
442
868
571
790
893
571
790
Boiler Output
Needed For
Maximum
Performance
(BTU/Hr)
112,000
118,000
116,000
125,000
132,000
118,000
127,000
141,000
221,000
220,000
236,000
232,000
240,000
428,000
428,000
40
Boiler
Pressure
Water Flow
Through
Through Coil
Coil
Gal/Min
(Ft. Water)
14.0
14.0
14.0
14.0
14.0
14.0
14.0
14.0
14.0
14.0
21.0
14.0
21.0
28.0
28.0
PN 240012875 REV. C [10/01/2021]
Drop
5.7
5.9
5.6
6.2
6.4
5.9
6.2
6.7
10.5
10.3
15.8
10.8
16.7
13.0
13.0