Carrier PG96VTA Installation, Start-Up, Operating And Service And Maintenance Instructions page 54

Two--stage, non--communicating, variable speed ecm, 4--way multipoise condensing gas furnace
Table of Contents

Advertisement

Sidewall Terminations
Concentric Vent
NOTE: Follow the instructions of the vent terminal manufacturer.
These instructions are provided as a reference only.
Determine an appropriate location for termination kit using the
guidelines provided in section "Locating The Vent Termination" in
this instruction.
1. Cut one 4- -in. diameter hole for 2- -in. kit, or one 5- -in. diam-
eter hole for 3- -in. kit.
2. Loosely assemble concentric vent/combustion air termina-
tion components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through
hole.
NOTE: Do not allow insulation or other materials to accumulate
inside of pipe assembly when installing it through hole.
4. Locate assembly through sidewall with rain shield posi-
tioned no more than 1- -in. (25 mm) from wall as shown in
Fig. 40.
5. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping. DO NOT CE-
MENT POLYPROPYLENE FITTINGS.
2-Pipe and 1-Pipe Vent Termination
NOTE: Follow the instructions of the vent terminal manufacturer.
These instructions are provided as a reference, only.
NOTICE
RECOMMENDED SUPPORT FOR VENT
TERMINATIONS
It is recommended that sidewall vent terminations in excess of
24 inches (.6 M) in vertical length be supported by EITHER
the Direct Vent Termination Kit shown in Table 12 or by
field- -supplied brackets or supports fastened to the structure.
Determine an appropriate location for termination kit using the
guidelines provided in section "Locating The Vent Termination" in
this instruction.
1. Cut two holes, one for each pipe, of appropriate size for
pipe size being used.
2. Loosely install elbow in bracket (if used) and place assem-
bly on combustion- -air pipe.
3. Install bracket as shown in Fig. 40 and 49.
NOTE: For applications using vent pipe option indicated by
dashed lines in Fig. 40 and 41, rotate vent elbow 90_ from
position.
4. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping. DO NOT CE-
MENT POLYPROPYLENE FITTINGS.
(Direct Vent / 2-Pipe System ONLY)
When two or more furnaces are vented near each other, two vent
terminations may be installed as shown in Fig. 40, but next vent
termination, or pair of vent terminations, must be at least 36 in.
(914 mm) away from the first two terminations. It is important that
vent terminations be made as shown in Fig. 40 to avoid
recirculation of vent gases.
Inducer Outlet Restrictor
To improve efficiency and operation of 40K, 60K or 100K BTUH
input models on very short vent systems, an inducer outlet
restrictor is required to be installed on the outlet of the inducer
assembly. The outlet restrictor is shown in the footnote of Table 13
- -Maximum Equivalent Vent Length. The outlet restrictor for 40K
models is shipped in the loose parts bag. See Table 13 for usage,
part numbers and sourcing of 60K and 100K inducer outlet
restrictors.
To determine if the outlet restrictor is required, see Table 13.
Failure to use an outlet restrictor on the 40K model when
required may result in flame disturbance or flame sense
lockout.
To install the outlet restrictor:
1. Remove the vent elbow from the inducer outlet.
2. Align the lock tabs on the outlet restrictor with the slots on
inside outlet of the inducer assembly.
3. Snap the outlet restrictor in place.
4. Re-install the vent elbow.
5. Torque vent elbow clamp 15-lb- -in.
54

Advertisement

Table of Contents
loading

Table of Contents