Haier SUPER MATCH AS35S2SF2FA-CL Service Manual page 18

Wall mounted type dc inverter
Table of Contents

Advertisement

7.1.4
Heating operation mode.
* temperature control range: 16---30℃
* temperature difference:
* control feature: the temperature compensation is automatically added and the system will send the
heating signals to the outdoor system.
If Tr+0.5℃≤Ts, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode.
If Tr>Ts+1.5℃, the outdoor system is turned off, the indoor fan will be at the heat residue sending mode.
*Indoor fan control
manual control: You can choose high, medium, low and automatic speed control.
Automatic: When Tr<Ts, high speed.
When Ts≤Tr≤Ts+2℃, medium speed.
When Tr> Ts+2℃, low speed.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 3
minutes (remain at high speed for 3 minutes.) before the next switch.
*Airgate location control: the location for the airgate can be set according to your needs.
Coldair proof operation
1. The fan control functions as below:
37
(THHOT4)
35
23
* Residue heat sending. The indoor fan will send the residue heat at a low speed for 20 seconds.
If other conditions are satisfied, when the compressor stops, the indoor system will operate at a light
speed. The indoor fan will stop when the coil temperature is below the THHOT0.
* Defrosting. When the system receives the defrosting signal from outdoors, the indoor fan will stop and
the indoor temperature display won't change. At the time, any indoor coil malfunctions will be neglected.
When the outdoor defrosting finishes, the coil malfunction will still be neglected until the compressor has
been started up for 30 seconds. The indoor temperature display will not change and the system
operates at the cold air proof mode.
* Automatic heating temperature compensation: when the system enters the heating mode, the
temperature compensation (4℃) will be added. When the status is switched off, the compensation will
be erased.
7.1.5
Strength operation
The system enters the mode after receiving the 'strength signal'.
±1℃
set
medium speed
low speed
weak speed
stop
37
(THHOT3)
35
(THHOT2)
25
(THHOT1)
16
(THHOT0)
15
Functions and Control
Domestic air conditioner

Advertisement

Table of Contents
loading

Table of Contents