Viessmann Vitoclima 300-S Service Instructions For Contractors page 23

Multi-split air-conditioning unit with inverter technology comprising an external unit and an internal device
Hide thumbs Also See for Vitoclima 300-S:
Table of Contents

Advertisement

Diagnosis
(cont.)
Fault
Fault
code
07
No feedback external fan/com-
pressor
08
Processor fault external fan
09
External fan idle
10
Max. speed of the external fan
exceeded
11
Compressor processor fault
12
Compressor idle
13
Max. compressor speed ex-
ceeded
14
Excessive compressor power
consumption
15
DC undervoltage
16
DC overvoltage
17
AC undervoltage
18
No connection to the internal
device A
19
No connection to the internal
device B
20
No connection to the internal
*
device C
21
No connection to the internal
device D
*1
Not applicable to type OT307H.
1
Troubleshooting
Cause/Remedy
Check the connections of the ex-
ternal fan (voltage and velocity
sensor); check the fan motor;
check the compressor connec-
tion and motor
Overheating/overvoltage at the
external fan controller; air inlet
blocked; motor jumper incor-
rectly placed on the controller;
check external fan motor
Check external fan
Wind-influenced excess air inlet
on the suction side; if required, fit
wind break; electromagnetic
faults
Overheating/overvoltage at the
compressor speed controller; air
inlet blocked; check compressor
motor
Checking the compressor
Restart; if problem persists, re-
place controller
Checking the compressor
DC voltage below limit; replace
controller
Check mains voltage (max.
264 V~); if OK then replace con-
troller
Check mains voltage (min.
198 V~); if OK then replace con-
troller
Check the connecting cable be-
tween the internal device, the ex-
ternal unit and earth
23