Viessmann Vitoclima 300-S Service Instructions For Contractors page 22

Multi-split air-conditioning unit with inverter technology comprising an external unit and an internal device
Hide thumbs Also See for Vitoclima 300-S:
Table of Contents

Advertisement

Troubleshooting
Diagnosis
(cont.)
A Three-digit display
B Key "Back"
C Key "Select"
D Key "Continue"
E Key "Exit"
Note
Only one fault code will be displayed, even if several faults have occurred.
To display further fault codes:
Switch the unit OFF and isolate it from the power supply.
Remove the fault.
Call up the diagnostic function again.
Fault codes external unit, type OT307H
Fault
Fault
code
01
Temperature sensor at the heat
exchanger of the external unit
02
Compressor temperature sen-
sor
03
Processor temperature sensor
04
Outside temperature sensor
05
Wet steam temperature sensor
06
Suction gas temperature sensor
22
Select the required parameter with
B/D.
Acknowledge the selection with C.
Call up the highest level with E.
Select diagnosis (dIA).
Select external unit/internal device:
oXX Fault code external unit
AXX Fault code internal device A
bXX Fault code internal device B
CXX Fault code internal device C
dXX Fault code internal device D
XX represents the fault code.
Cause/Remedy
Check sensor connection;
replace sensor