The instructions must be fully observed to ensure personal safety and the safety of others, and to protect equipment and ensure the correct operation of the VEX unit. EXHAUSTO A/S accepts no liability for accidents caused by a failure to use the product in accordance with the manual’s instructions and specifications.
1.1.1 Designations used and key to wiring diagram Designation Supplied by Control system panel EXHAUSTO VEX unit EXHAUSTO Connection box for heating coil/cooling unit EXHAUSTO Distribution board fuses...
Connection in automatic switchboard 3005999-2020-10-20 1.2 Electrical diagrams 1.2.1 Connection diagram - 1-phase * Not EXHAUSTO delivery ** 120 Ω resistance for end termination *** Crown sleeve for continuation of 24 VDC **** Only if HW (water) ***** Only if MCOCW / MXHP...
Connection in automatic switchboard 3005999-2020-10-20 1.2.3 Termination The first and last device on the bus must be terminated. The diagrams below show two termination examples. See position of jumper JP2 on EXact2 Main Board in section “Terminal board on EXact2 Main Board”. then See diagram no.
Connection in automatic switchboard 3005999-2020-10-20 1.3 Electrical diagrams - Cable plan The cable plan below shows the accessories that can be connected to the control system panel. 1.4 Internal cable and wiring 1.4.1 Wiring diagrams The following wiring diagrams show internal connections 1.4.2 Designation and key to wiring diagram Accessories are a direct customer choice, and the options may be generated from several factors.
Page 9
Connection in automatic switchboard 3005999-2020-10-20 Designation Standard Accesso- Option ries Control system panel VEX unit -B20 Automatic overheating switch 50°C outdoors -B21 Manual overheating switch 80°C in electric heating coil electric heating coil (HE1/ HE2) in supply air chamber Control fuse EXact2 AHUC PCB EMC filter Passive motor filter...
Page 10
Connection in automatic switchboard 3005999-2020-10-20 Designation Standard Accesso- Option ries □ Terminal row 2,5 10/28...
Connection in automatic switchboard 3005999-2020-10-20 1.4.8 Internal wiring and hoses * Set termination to ON (DIP switch 8) on the last of up to three MPT's. The number of configured MPT's may be from one to three (-P1, -P2 and -P3) 16/28...
Installation of the VEX unit 3005999-2020-10-20 2. Installation of the VEX unit 2.1 Scope of installation 2.1.1 Connections in the control system panel See following table for possible connections to the terminal block on the EXact2 cir- cuit board. Possible connections See section Supply voltage 2.2 Dimensioning and installation...
Page 18
Installation of the VEX unit 3005999-2020-10-20 The inclusion of a built-in control fuse depends on the size of the VEX unit and the size of the VEX unit’s internal electric heating coils (HE1/HE2). See the overview below to see when the VEX unit has a built-in control fuse. ●...
Installation of the VEX unit 3005999-2020-10-20 ● PFI type A breaker in accordance with EN 61008 that breaks the circuit on registering a vagrant current with DC content (pulsating DC) ● The RCCBs must be marked with the following symbol: ●...
Page 20
Installation of the VEX unit 3005999-2020-10-20 With HW or CW coil (supply air) Supply voltage Max. phase current [A] VEX size (nominal) Composite Aluminium 310T 1x230V+N+PE ~ 50/60Hz 320T 1x230V+N+PE ~ 50/60Hz 330T 1x230V+N+PE ~ 50/60Hz 340T 1x230V+N+PE ~ 50/60Hz 350T 1x230V+N+PE ~ 50/60Hz 14.3...
Installation of the VEX unit 3005999-2020-10-20 Circulation pump If the VEX unit is equipped with an internal HW coil, the circulation pump can be connected to terminal block -X1 (terminals 12 and 14). The circulation pump may not draw more than 2.0 A, and its cable must be dimensioned in accordance with the VEX unit’s fuse.
Installation of the VEX unit 3005999-2020-10-20 2.3 Electrical components 2.3.1 Control system panel The illustration below shows the electrical components’ positioning in the control sys- tem panel: -K23 -K12 -K21 or -K24 -K22 Alternativ -K25 Component list Code Electrical component Qty.
Installation of the VEX unit 3005999-2020-10-20 2.3.2 Terminal block on the EXact2 printed circuit board The drawing and diagram below show which components (standard + accessories) can be connected to the terminal block terminal block. Designation Terminal block no. Connection of the following components 1 - 4 Bus for external topics 5 - 8...
Page 24
Installation of the VEX unit 3005999-2020-10-20 Designation Terminal block no. Connection of the following components AUX OUT 35 - 36 Fire alarm for controlling smoke evacuation damper or fire gas fan. Light/CP 37 - 38 Light / circulation pump. Light is not a possible option on the VEX350T, but if VEX units are equipped with HW drums, the circula- tion pump (CP function) is activated.
Installation of the VEX unit 3005999-2020-10-20 2.3.3 Connecting shielded cable to MODBUS Cable type □ MODBUS requires shielded cable of type 2 x 2 x 0.25 twinned pair conductors. Connection Wires and screen must be connected as shown in the table below Wires Step Action...