6.2 Brief Description of Modes and Functions

1. Temperature Parameters
Indoor preset temperature (Tpreset)
Indoor ambient temperature (Tamb.)
2. Basic Functions
Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory function
is available, for the first energization, if the compressor is at stop before de-energization, the compressor will be started without a
3-minute lag; if the compressor is in operation before de-energization, the compressor will be started with a 3-minute lag; and once
started, the compressor will not be stopped within 6 minutes regardless of changes in room temperature;
(1) Cooling Mode
① Working conditions and process of cooling
Cooling conditions and process(09k)
a. When Tamb.≥Tpreset the unit starts cooling. In this case, the IDU fan motor, ODU fan motor and compressor run, and the IDU fan
motor runs at set speed;
b. When Tamb.=Tpreset-3℃ , the compressor continuously operates below the frequency of 15Hz (not including 15Hz) for 15mins. If
Tamb.=Tset-3℃ still keeps the same, the compressor stops operation;
c. When Tamb.≤Tpreset-4℃ , the compressor stops operation; ODU fan motor stops operation with a delay of 30s and IDU fan motor
operates at set speed;
d. When Tpreset-2℃< Tamb. < Tset, the unit will maintain its previous running status.
Cooling conditions and process(12k)
a.When Tamb.+Tindoor supplementary≥Tpreset, the unit starts cooling. In this case, the IDU fan motor, ODU fan motor and
compressor run, and the IDU fan motor runs at set speed;
b. When Tamb.+Tindoor supplementary≤Tpreset-2℃ , the compressor stops operation; ODU fan motor stops operation with a delay
of 30s and IDU fan motor operates at set speed;
c.When Tpreset-2℃< Tindoor amb.+Tindoor supplementary < Tpreset, the unit will maintain its previous running status.
Under this mode, the four-way valve will be de-energized and temperature can be set within a range from 16 to 30
If the compressor is shut down for some reason, the indoor fan and the swing device will operate at original state.
Protection
◆ Antifreeze protection
Under cooling and dehumidifying mode, 6 minutes after the compressor is started:
o
If T evap≤2
C, the compressor will operate at reduced frequency.
o
If T evap≤-1
Cis detected for durative 3 minutes, the compressor will stop, and after 30 seconds, the outdoor fan will stop; and under
cooling mode, the indoor fan and the swing motor will remain at the original state.
o
If T evap. ≥10
Cand the compressor has remained at OFF for at least 3 minutes, the compressor will resume its original operation
state.
◆ Total current up and frequency down protection
If I
≤6, frequency rise will be allowed; if I
total
frequency; and if I
≥9, the compressor will stop and the outdoor fan will stop with a time lag of 30s.
total
(2) Dehumidifying Mode
① Working conditions and process of dehumidifying
If Tamb>Tpreset, the unit will enter cooling and dehumidifying mode, in which case the compressor and the outdoor fan will operate
and the indoor fan will run at low speed.
o
If Tpreset -2
C≤Tamb≤Tpreset, the compressor remains at its original operation state.
o
If Tamb.< Tpreset -2
low speed.
② Protection
Protection is the same as that under the cooling mode.
(3) Heating Mode
16
≥7, frequency rise will not be allowed; if I
total
C, the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will operate at
o
C.
≥8, the compressor will run at reduced
total