RKI 65-2336RK Operator's Manual

Carbon monoxide transmitter

Advertisement

Quick Links

65-2336RK
Carbon Monoxide Transmitter
Operator's Manual
Part Number: 71-0178RK
Revision: B
Released: 7/6/20
RKI Instruments, Inc.
www.rkiinstruments.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 65-2336RK and is the answer not in the manual?

Questions and answers

Summary of Contents for RKI 65-2336RK

  • Page 1 65-2336RK Carbon Monoxide Transmitter Operator’s Manual Part Number: 71-0178RK Revision: B Released: 7/6/20 RKI Instruments, Inc. www.rkiinstruments.com...
  • Page 2 Typical calibration frequen- cies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 2 • 65-2336RK CO Transmitter...
  • Page 3 Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
  • Page 4: Table Of Contents

    Parts List ..............21 4 • 65-2336RK CO Transmitter...
  • Page 5: Overview

    NOTE: The following symbol on the detector label is a caution to the user to refer to this documentation for installation and operation instructions: WARNING: When using the 65-2336RK, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 65-2336RK and to minimize the risk of personal injury.
  • Page 6: Description

    It consists of the CO detector, amplifier, and junction box. Controller Terminal Strip Factory Adjust Pot Span Pot Zero Pot Amplifier + Test Point (Red) Detector Terminal Strip - Test Point (Black) J-Box CO Detector Figure 1: CO Transmitter Component Location 6 • 65-2336RK CO Transmitter...
  • Page 7: Co Detector

    The sensor is secured within the detector assembly by the housing cap. Through a series of chemical and electrical reactions, the sensor produces an electrical output that corresponds to the detection range of the transmitter. 65-2336RK CO Transmitter • 7...
  • Page 8: Amplifier

    The test points are on the left side of the amplifier (see Figure 1). The test points produce a 100 mV to 500 mV output that corresponds to the transmitter’s 4 to 20 mA output. Use the test points and a voltmeter to measure the amplifier’s output during the start-up and calibration 8 • 65-2336RK CO Transmitter...
  • Page 9: Junction Box

    Select a site where the transmitter is not likely to be bumped or disturbed. Make sure there is sufficient room to perform start-up, maintenance, and calibration procedures. • Select a site that is at normal breathing level. 65-2336RK CO Transmitter • 9...
  • Page 10 CO Detector 1 1/2-20 Thread for Calibration Cup Figure 3: Mounting the CO Transmitter 2. At the monitoring site you select, hang or mount the junction box with the detector facing down (see Figure 3). 10 • 65-2336RK CO Transmitter...
  • Page 11: Wiring The Co Transmitter To A Controller

    10. Route the cable or wires leading from the CO transmitter through one of the conduit hubs at the controller housing. CAUTION: Do not route power and transmitter wiring through the same controller conduit hub. The power cable may disrupt the transmission of the transmitter signal to the controller. 65-2336RK CO Transmitter • 11...
  • Page 12 Figure 4: Wiring the CO Transmitter to a Controller 12. If shielded cable is used, connect the cable’s drain wire to an available chassis (earth) ground at the controller. RKI controllers typically have a ground stud that can be used to ground the cable’s drain wire.
  • Page 13: Startup

    The procedure below describes applying zero emission air, usually called zero air, using a calibration kit that includes a calibration cup, calibration gas, sample tubing, and a fixed flow regulator with an on/off knob. RKI Instruments, Inc. recommends using a 0.5 LPM (liters per minute) fixed flow regulator.
  • Page 14: Maintenance

    Calibrate the CO transmitter as described in “Calibration” on page 19 of this manual. See the calibration frequency discussion in “Calibration Frequency” on page 19 to determine if a quarterly calibration schedule fits your needs. 14 • 65-2336RK CO Transmitter...
  • Page 15: Troubleshooting

    Unexplained • Controller indicates • Charcoal filter is 1. Replace charcoal filter. a CO reading that saturated and no Upscale 2. If difficulties continue, contact RKI cannot be verified. longer scrubbing out Readings or for further instructions. interfering gases. Alarms •...
  • Page 16: Replacing Components Of The Co Transmitter

    10. Turn on or plug in power to the controller. 11. Turn on the controller and place into normal operation. CAUTION: Allow the replacement sensor to warm up for 5 minutes before you continue with the next step. 16 • 65-2336RK CO Transmitter...
  • Page 17 TOXIC+ and the black wire to the terminal labeled TOXIC-. See Figure 4 for the detector wiring connections to the amplifier. 9. Reinstall the detector terminal strip into its socket. 10. Turn on or plug in power to the controller. 65-2336RK CO Transmitter • 17...
  • Page 18 10. Turn on or plug in power to the controller. 11. Turn on the controller and place it into normal operation. 12. Allow the transmitter to warm up for 5 minutes. 13. Calibrate the CO transmitter as described in “Calibration” on page 19. 18 • 65-2336RK CO Transmitter...
  • Page 19: Calibration Frequency

    It describes the test using a calibration kit that includes a calibration cup, calibration gas, sample tubing, and a fixed flow regulator with an on/off knob. RKI Instruments, Inc. recommends using a 0.5 LPM (liters per minute) fixed flow regulator.
  • Page 20: Setting The Zero Reading

    4. When the display reading falls below the alarm setpoints, return the controller to normal operation. 5. Verify that the controller display reading decreases and stabilizes at 0 ppm. 6. Store the components of the calibration kit in a safe and convenient place. 20 • 65-2336RK CO Transmitter...
  • Page 21: Parts List

    CO transmitter (includes detector and amplifier), CSA classified 65-2438 CO replacement detector assembly (includes sensor), CSA classified 71-0178RK 65-2336RK CO Transmitter Operator’s Manual (this document) 81-0064RK-01 Calibration cylinder, 50 PPM CO in air, 34 liter steel 81-0076RK-01 Zero air calibration cylinder, 34 liter steel 81-1050RK Regulator with gauge and knob, 0.5 LPM, for 17 liter and 34 liter steel...