Camus Hydronics Dynaforce Series Installation And Service Manual page 33

Table of Contents

Advertisement

4-20mA/ 2-10Vdc Firing Rate Operation (Standalone)
Description
Boiler operates with variable
setpoint determined by 4-
20mA incoming signal
Modulates on header sensor
Heat demand is generated
when Remote Operator is
closed and 4-20mA or 2-
10Vdc signal is present.
System Sensor Enable (Standalone)
Description
Method to enable system
sensor for Standalone
applications
Electrical Connection(s)
Electrical Connection(s)
Programming Instructions
1) Place toggle switch in LOCAL
2) Press
and
3) Press [Lead Lag Master Configuration]
4) Press [Advanced Settings >]
5) Press the
to arrive at Central Heat
6) Select Modulation rate source = S2 (J8-6) 4-20mA and burner on/off
7) Place toggle switch to REMOTE for remote operation (if required)
Programming Instructions
1) Press
and
2) Press [Sensor Configuration]
3) Select S5 (J8-11) Sensor: 10K NTC Single Non-Safety
4) The control will proceed into a Lockout 2 condition
5) Press [Verify] > [Begin] > [Yes]
6) Press the reset button on the ignition control within the alotted time
33