A service clearance of 24" must be provided above the
top panel to allow access to the burner.
The appliance must be installed so that the ignition
system
components
(dripping, spraying, etc.) during appliance operation
and
service
(circulator
replacement, etc.)
Appliances located in a residential garage and in
adjacent spaces that open to the garage and are not
part of the living space of a dwelling unit must be
installed so that all burners and burner ignition devices
have a minimum clearance of not less than 18" (46cm)
above the floor. The appliance must be located or
protected so that it is not subject to physical damage
by a moving vehicle.
DO NOT install this appliance in any location where
gasoline or flammable vapors are likely to be present.
DO NOT install this appliance on top of carpet flooring
Appliance must be installed on a level floor. Maintain
required clearances from combustible surfaces.
The appliance designed for indoor installation (Indoor
Models) must be installed indoors where it is protected
from exposure to wind, rain and weather.
The appliance designed for outdoor installation
(Outdoor Models) must be installed outdoors. For
outdoor installations, always consider the use of a
shelter such as a garden shed in lieu of direct exposure
of the appliance to the elements. The additional
protection afforded by the shelter will help to minimize
nuisance problems with electrical connections and will
allow easier servicing of the appliance under severe
weather conditions.