15. Troubleshooting Guide

15.1 Self Diagnosis Function

The display screen of wireless remote control unit and the self-diagnosis LEDs (green) on the outdoor printed
circuit board in the outdoor unit can be used to identify the location of the problem.
Refer to the table below to identify and solve the cause of the problem, and then re-start the air conditioner
system.
If the problem is solved and operation returns to normal.
LED 1 illuminates and others LED are off.
Abnormality
Diagnosis
or
LED 6 LED 5 LED 4 LED 3 LED 2 LED 1
display
protection
control
H11
Indoor/outdoor
abnormal
communication
H12
Indoor unit
capacity
unmatched
H15
Compressor
temperature
sensor
abnormality
H16
Outdoor
current
transformer
(CT)
abnormality
H27
Outdoor air
temperature
sensor
abnormality
H28
Outdoor heat
exchanger
temperature
sensor 1
abnormality
H32
Outdoor heat
exchanger
temperature
sensor 2
abnormality
H33
Indoor/
outdoor
misconnection
abnormality
H36
Outdoor gas
pipe
temperature
sensor
abnormality
Abnormality
judgement
O
After
operation for
1 minute
O
90s after
power supply
O
O
Continuous
for 5s
O
O
O
O
Continuous
for 5s
O
O
O
Continuous
for 5s
O
Continuous
for 5s
O
O
O
O
Continuous
for 5s
30
Protection
operation
Indoor fan only
Indoor/outdoor
operation can
communication not
start by
establish
entering into
force cooling
operation
Total indoor
capability more than
maximum limit or
less than minimum
limit, or number of
indoor unit less than
two.
Compressor
temperature sensor
open or short circuit
Current transformer
faulty or compressor
faulty
Outdoor air
temperature sensor
open or short circuit
Outdoor heat
exchanger
temperature sensor 1
open or short circuit
Outdoor heat
exchanger
temperature sensor 2
open or short circuit
Indoor and outdoor
rated voltage
different
Heating
Outdoor gas pipe
protection
temperature sensor
operation only
open or short circuit
Problem
Check location
 Indoor/outdoor
wire terminal
 Indoor/outdoor
PCB
 Indoor/outdoor
connection wire
 Indoor/outdoor
connection wire
 Indoor/outdoor
PCB
 Specification and
combination table
in catalogue
 Compressor
temperature
sensor lead wire
and connector
 Outdoor PCB
faulty or
compressor
faulty
 Outdoor air
temperature
sensor lead wire
and connector
 Outdoor heat
exchanger
temperature
sensor 1 lead
wire and
connector
 Outdoor heat
exchanger
temperature
sensor 2 lead
wire and
connector
 Indoor and
outdoor units
check
 Outdoor gas pipe
temperature
sensor lead wire
and connector