OPERATING LIMITATIONS AND SOUND POWER DATA

YORK INTERNATIONAL
OPERATING LIMITATIONS – SI UNITS
LEAVING CHILLED LIQUID TEMP ( °C)
CHILLED WATER TEMP DIFFERENCE ( °C)
WATER SIDE PRESSURE (BAR)
REFRIGERANT SIDE PRESSURE (BAR)
MODEL
YCAS
0295EB
0335EB
0375EB
0425EB
0475EB
0515EB
0555EB
0575EB
0605EB
AIR
ENTERING
CONDENSER (°C)
FAN
AVAILABLE STATIC
HIGH PRESS. FANS OPTION 1
PRESSURE (Pa)
HIGH PRESS. FANS OPTION 2
SLOW SPEED FANS
ELECTRICAL THREE PHASE 50 Hz (V)
* Maximum Ambient w/ High Ambient Kit is 54°C.
MIN
MAX
5.0
13
3
10
10
20
EVAPORATOR FLOW
LITERS/SECOND
MIN.
MAX.
6.9
25.4
7.7
25.4
8.6
25.4
9.5
37.9
10.6
42.3
11.7
46.9
12.4
48.5
13.1
48.5
13.6
48.5
STANDARD FANS
–18
46
STANDARD FANS
20
85
150
10
380
FORM 201.19-NM7 (804)
7