Log in to the FusionSolar app, on the Device Commissioning screen, choose
Maintenance > Optimizer disconnection detection, tap the detection button,
and rectify the fault based on the detection result.
Figure 4-5 Optimizer disconnection detection

4.3 Rapid Shutdown

When the output is disconnected or the inverter shuts down, the optimizer can
adjust the module output voltage to a safe range to ensure the safety of the
construction and O&M personnel as well as firefighters.
If optimizers are configured for all PV modules, the PV system can perform a rapid
shutdown to decrease the output voltage to below 120 V within 15s and to below
30 V within 30s.
Perform the following steps to trigger a rapid shutdown:
Issue 01 (2021-10-30)
NO TE
● The rapid shutdown function is not supported if optimizers are configured for some PV
modules.
● You are advised to periodically check whether the rapid shutdown function is normal.
Method 1: Turn off the AC switch between the inverter and the power grid.
Method 2: Connect a switch to the DI and GND ports of the inverter to form a
circuit. (For details about the DI port, see the corresponding inverter user
manual.) The switch is turned on by default. Turn off the switch to trigger a
rapid shutdown.