Carrier 110 Series Installation, Start-Up, Operating And Service And Maintenance Instructions page 53

Single stage 4 -way multipoise condensing gas furnace
Table of Contents

Advertisement

1. Attach vent pipe adapter with gasket to furnace casing.
2. Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
3. Slide vent pipe through adapter and coupling into vent elbow.
4. Insert vent pipe into vent elbow.
5. Torque all clamps 15 lb.- -in.
6. Attach combustion air pipe adapter with gasket to furnace.
7. Attach combustion air pipe to adapter with silicone. Pilot drill a1/8- -in. hole in adapter and secure with a #7 x 1/2- -in. sheet metal
screw.
VENT PIPE FLUSH WITH ADAPTER
NOTES FOR VENTING OPTIONS
VENT PIPE ADAPTER WITH GASKET
INSTALLED ON FURNACE VENT
PIPE IS CUT FLUSH WITH TOP OF
ADAPTER. PRIME AND CEMENT VENT
PIPE TO ADAPTER. ALLOW TO DRY
BEFORE INSTALLING VENT COUPLING.
Fig. 43 - - Vent Pipe Flush with Adaptor
Point elbow down towards
back of furnace
12" (256mm) minimum
60"(1524 mm) or
1 additional elbow maximum
CASING SIDE ATTACHMENT
COMBUSTION AIR PIPE
(NON-DIRECT VENT)
Fig. 44 - - Combustion Air Pipe Attachment
VENT PIPE FLUSH SHOWING COUPLING
to
53
ALIGN NOTCHES IN VENT PIPE
COUPLING OVER STAND-OFF
ON ADAPTER. TORQUE LOWER
CLAMP 15 LB-IN. WHEN REMAINING
VENT PIPE IS INSTALLED, TORQUE
UPPER CLAMP TO 15 LB-IN.
A13076
L12F042