olympia electronics GR-579/L/90/WP Quick Start Manual

olympia electronics GR-579/L/90/WP Quick Start Manual

Waterproof self testing maintained emergency led luminaires

Advertisement

Quick Links

Manual TEST or Resetting Errors with the A-1900 Test card (not included and is available
only after request). In order to test or reset the device you must place the card on the side of the
indications and remove it instantly for TEST or remove it after the reset is conducted (the
indications light in sequence).
LED INDICATIONS
Battery replacement
It can be done only by a competent person and after the mains interruption.
Step 1. Remove the front cover by unscrewing the retaining screws. Remove the acrylic plate.
Step 2. Unfasten the screws to remove the plastic cap and the battery's plastic holder (photo 3).
Step 3. Remove the old battery and place a new on of the same type and characteristics.
Connect the battery's cable as shown in the photo 4.
Step 4. Replace the removed parts (previous steps 1,2).
2
Photo 3
LED MODULE CHARACTERISTICS
GR-579/L/90/WP
Manufacturer
Model Number
Voltage Range
Nominal Power
Connections
Temperature (tc)
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully
agreed to them in writing. Products that have been damaged can be returned to the premises of our
company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
info@olympia-electronics.gr
Page 4 from 4
A-1900
Test card
3
Photo 4
GR-579/L/180/WP
Olympia Electronics S.A
0105153
11.6-14.4VDC
10.4W
Cable connection with polarity
50 °C max. across the board
923579000_09_004
WATERPROOF SELF TESTING MAINTAINED EMERGENCY LED LUMINAIRES
TECHNICAL CHARACTERISTICS
GR-579/L/90/WP
(for LED MODULE Specs. see page 4)
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
2x4.8V/1.5Ah
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
LIGHT SOURCE INTENSITY (230V AC/emerg.)
DEGREES OF COVER PROTECTION
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Congratulations for your selection to buy this product.
Olympia Electronics - European manufacturers.
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply. In normal
operation (L1 connected to L) the led strip
lights and the battery is charging. In case of
a mains power supply failure the luminaire will
light the led strip automatically in emergency
mode (powered by its battery). When the
mains power supply is restored the device
turns to normal operation.
OPERATION
Battery Charging
The battery charging is completely controlled.
In this case, the best possible
battery
maintenance is achieved, as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Battery Cut-off
The luminaire enters in this operation when
the mains power supply fails and battery has
lost its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Page 1 from 4
GR-579/L/180/WP
220-240V AC/50-60Hz
2x9W / 2x9.5VA - PF: 0.95/230V
2x4.8V/3Ah
From overcharge and deep discharge
Charge LED, Lamp Fault LED, Battery LED
24 h
90 min
180 min
White LEDs
2x680lm / 2x340lm
IP66
o
5 to 40 C
Up to 95%
Painted steel plate (RAL 7036), ABS/PC, PC
740 x 400 x 185 mm
11550gr
11730gr
3 years (1 year for the batteries)
Manual Test
This test can be done by placing the test card
on the side of the indications (page 4)
remove it instantly. An operation test is initiated
and the light source and the emergency circuit
of the device is monitored. The manual test can
be conducted only if the mains power supply
and the battery is connected. During this test
period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
and emergency duration. This test is conducted
automatically every 6 months. In order to be
performed, the mains power supply and the
battery should be connected and fully charged.
If the battery is not fully charged, the test is
postponed until the battery is completely
charged. If during this test, the autonomy is less
than nominal, then the battery fault led turned
on continuously and the battery must be
replaced.
923579000_09_004
and

Advertisement

loading

Summary of Contents for olympia electronics GR-579/L/90/WP

  • Page 1 The luminaire enters in this operation when battery should be connected and fully charged. Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the the mains power supply fails and battery has If the battery is not fully charged, the test is buyer depending on the reason of defection.
  • Page 2 Back Up Operation 2. The device must be connected to the The autonomous duration of battery during m a i n s p o w e r s u p p l y t h r o u g h a f u s e emergency mode is at least the one that is dependent on the total amount of the line’s stated...

This manual is also suitable for:

Gr-579/l/180/wp