Calculation Of Upstream And Downstream Distances - Honeywell GENT Venturi-Air Duct Kit Installation Instruction

Table of Contents

Advertisement

S4-34760_Venturi-Air Duct Kit
2.2

Calculation of upstream and downstream distances

Air duct with circular cross-section
2 x H x B
d
=
h
H
B
In order to prevent incorrect measurements the air through the duct detector should be in the same direction as
the air flow through the duct. For applications with a detector mounting close to reducing dampers and
regulating flaps, filter units or bends, the following minimum distances must be observed:
upstream
downstream
Fig. 3: Air duct detector after a bend in the duct system and downstream from an air intake (Example)
6
www.acornfiresecurity.com
H + B
at least 3 x the nominal diameter of the air duct
at least 5 x the nominal diameter of the air duct
www.acornfiresecurity.com
Air duct with rectangular cross-section
d
= D
h
D
4188-971_issue 1_07/09_duct sensor kit