Mounting The Air Duct Kit - Honeywell GENT Venturi-Air Duct Kit Installation Instruction

Table of Contents

Advertisement

Dimensions
180
146
235
27
Fig. 1: Dimensions
2.1

Mounting the air duct kit

The required mounting position is indicated by the arrow
bottom of the enclosure provides a quick info for the correct positional arrangement of the air duct kit.
Fig. 2: Mounting and orientation of the air duct detector
4188-971_issue 1_07/09_duct sensor kit
www.acornfiresecurity.com
www.acornfiresecurity.com
S4-34760_Venturi-Air Duct Kit
183
70
35
on the top of the enclosure. The arrow shaped
Mount the kit with the supplied three long screws
on the duct. Only the three marked holes may be
used to fasten the kit on the air duct.
The kit can be mounted in different positions (top,
side, bottom) on the air duct without affecting the
proper operation.
The arrow
on the housing of the air duct kit
must point into the direction of the air flow.
The Venturi tube must be aligned in the middle of
the ducts diameter and lead into the duct.
5