SiUS121736EA
Wireless Remote
(1) Remove the cover and take it off.
(2) Cut the address setting jumper.
Controller
ARC452 series
Caution
Replace the remote controller if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut a wrong
jumper.
5.2.4 Jumper and Switch Settings
CTXG, FTXR, CTXS, FTXS, CDXS, FDXS, FVXS series
FVXS series only
For the location of the jumper, refer to the following pages.
Trial Operation and Field Settings
Jumper
ADDRESS
EXIST
1
CUT
2
Jumper (on indoor
unit PCB)
JB
Fan speed setting
when compressor
stops for thermostat
OFF. (effective only
at cooling operation)
JC
Power failure
recovery function
Switch (on indoor unit
PCB)
SW2-4
Upward airflow limit
setting
CTXG09/12/18QVJUW(S), FTXR09/12/18TVJUW(S): page 26
CTXS07LVJU, FTXS09/12LVJU: page 28
FTXS15/18/24LVJU: page 30
CDXS07/15/18/24LVJU, FDXS09/12LVJU: page 32
FVXS09/12/15/18NVJU: page 34
ARC466 series
Jumper
ADDRESS
EXIST
CUT
(R12065)
∗ Do not cut the left jumper.
Function
When connected
(factory set)
Fan speed setting;
Remote controller
setting
Auto-restart
Function
OFF
(factory setting)
Exposed or half
embedded
installation
Field Settings
1
2
When cut
The fan stops.
The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.
ON
Set the switch to ON position
when you install the indoor unit
embedded in the wall to avoid
condensation.
(R18416)
236