 1 .Mountingpreparations

Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision of
qualified skilled electrical personnel in
accordance with electrical regulations.
Disconnect supply before installing!
The device is not suited for safe dis-
connection of the mains supply.

When in Master/ Slave mode of
operation, the Master-appliance must
always be installed at the location
where there is least daylight.
2c.Selftestcycle
The product enters an initial 60-second
self-test cycle, when the supply is first
connected. The occupancy detector is
ready for operation.
During the selftest cycle, the following
settings can be made:
Light stop active: (A)
Light off active: (B)
(see point 7)
Option:
IR-PD4-GH
Wallbracketforremotecontrol
IR-PD4-GH
IR-PD-Mini
®
2a.  I nstallationoftheLUXOMAT
C
The detector must be in stalled on a solid and
level surface. The circular cover ring must be removed
close
prior to assembly. To do this, twist the lens (C) anti-
open
clockwise through approximately 5° and lift off.
Having connected up the wires in accordance with
regulations, secure the detector with 2 screws.
After installation replace the lens and lock (turn clock-
wise). Mains to be connected.
ATTENTION: Install the unit in such a manner that
both markings on the housing are positioned in the
longitudinal axis of the area to be monitored (e.g.
high-bay corridors)
 3 .Puttingintooperation/Settings
Factory settings
The PD4-M-1C-GH is preset with time setting 5 min. and twilight switch
1000 Lux.
Attention:
Changes to the settings can only be made by remote control IR-PD4-GH.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between
2 pulses sent to the master. The setting can be made
9s
2s
with activated ( ) or deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be
LED ON
set.
LED OFF
4. P D4-M-1C-GH:Settingscarriedoutusingremote
control(optional)
Remote control LUXOMAT
1. Check Battery:
Open battery compartment by pressing the plastic
springs together and removing the battery-holder.
Settings for master with remote control
Settings for relay
Channel 1:
Reset when
open: Deletes
��
all values set
or
��� ����
���
with the remote
control, loads
the default
settings
+
or
or
PD4-M-1C/-S-GH-SM
PD4-M-1C-GH-SM
®
IR-PD4-GH
®
Unlocking device
or
Adjust the target value
for brightness
��
��� ��
���
HA
OFF
Lock device
2b.Rangeindependencefromthemountingheight
Range (circular detection) T=17°C
Mounting
height
Walking across
2.00 m
r = 7.50 m
2.50 m
r = 9.00 m
3.00 m
r = 11.00 m
3.50 m
r = 13.00 m
4.00 m
r = 15.00 m
4.50 m
r = 17.00 m
5.00 m
r = 18.50 m
6.00 m
r = 18.50 m
7.00 m
r = 18.50 m
8.00 m
r = 22.00 m
9.00 m
r = 22.00 m
10.00 m
r = 22.00 m
r=radius / Ø=diameter
5.PD4-M-1C-GH-SM-Dimensions
L
L
N
N
L'
L'
70
98
Explanation of button functions
��
Target value for brightness
����
���
���
Automatic reading in of the current light value
as a new target light value
Sun button - specified twilight value
Daytime operation
��
��
Lag time
���
���
Pulse function, fully automatic mode active
Switch between fully automatic/semi-automatic mode
HA
HA
Semi-automatic mode active: Red + green LEDs flash 3x every
ON
OFF
5 seconds
Adjust the target value for brightness
to reach the calculated target value, increase the light value by
+
approx. 50 lux each time the button is pressed
Test mode when closed:
exited automatically after 3 minutes
Test mode when open:
not exited automatically
To deactivate: press reset
Reset when closed
The lighting relay is switched off, i.e. opened and the lag times
are reset.
Light on /off when closed
(A) The light remains on/off until movements are detected in
the detection area. After the last detected movement, the light
remains off for the duration of the set lag time. (B) If the "Light
stop" function was activated in the selftest cycle, the light is
switched off for 5 seconds (red and green LEDs flash). The device
then returns automatically to the selected operating mode (fully or
semi-automatic mode).
GB
Ø = 15.00 m
Ø = 18.00 m
Ø = 22.00 m
Ø = 26.00 m
Ø = 30.00 m
Ø = 34.00 m
Ø = 37.00 m
Ø = 37.00 m
Ø = 37.00 m
Ø = 44.00 m
Ø = 44.00 m
Ø = 44.00 m
98

Advertisement

loading

Summary of Contents for B.E.G. LUXOMAT PD4-M-1C-GH-SM

  • Page 1 B.E.G. ® Installation and Operating Instruction for B.E.G. -Occupancy detectors PD4-M-1C/-S-GH-SM  1 .Mountingpreparations 2a.  I nstallationoftheLUXOMAT PD4-M-1C-GH-SM 2b.Rangeindependencefromthemountingheight ® Range (circular detection) T=17°C Work on the 230 V mains supply The detector must be in stalled on a solid and...
  • Page 2 6. F ully / Semiautomaticmode 10.Wiringdiagrams 13.LED-functionalindicators,fault- finding for IR-PD functions see page 1 Standard mode with master 1-channel occupancy detectors (NO) with R and S terminal Fully automatic operation The functional indicators in the case of the In this operating mode, the lighting switches automati- PD4-M-1C-GH (red and green LED‘s) LUXOMAT ®...

This manual is also suitable for:

Pd4-m-1c-s-gh-sm