Undervoltage Trip - Toshiba HV6FS Instruction Manual

Vacuum circuit breakers
Table of Contents

Advertisement

OPERATION

UNDERVOLTAGE TRIP

All HV6FS fixed mounted circuit breakers are
furnished with an undervoltage trip device. The
undervoltage trip device operates to trip the
circuit breaker OFF unless 120VAC control
power is present at the terminals of relay UV.
When the circuit breakers are shipped, the
undervoltage trip device is defeated by a factory
installed plug (Fig. 30). If this plug is left in place,
the circuit breaker will operate normally without
power applied to relay UV. Removing this plug
(Fig. 31) activates the undervoltage trip function.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Fig. 30 Plug Installed in UV Trip Device
Fig. 31 Removing Plug From UV Trip Device
Page 25