Installation; Rating Verification - Toshiba HV6FS Instruction Manual

Vacuum circuit breakers
Table of Contents

Advertisement

Page 12
Do not install this
WARNING
equipment in areas where
unusual service conditions
exist. Using this equipment
in other than usual service
conditions can result in
equipment failure.
Toshiba HV6FS circuit breakers are intended for
use in usual service conditions as defined in
IEEE C37.20.2. The temperature of the cooling
air (ambient air temperature) surrounding the
breaker should be between the limits of -5°C
(23°F) and +40°C (104°F). The altitude of the
equipment installation should not exceed 3300 ft
(1000 m).
In particular, avoid the following installation
conditions:
Excessive dust
-
-
Corrosive gases
Extreme variations in temperature
-
-
Very high or low humidity
Vibrations
-
-
Inclined locations
If there is a chance that condensation can occur
R A T E D V O L T A G E
F R E Q U E N C Y
C O N T I N U O U S A M P S
I M P U L S E L E V E L
D I E L E C T R I C
W E I G H T
P A R T S & W I R I N G , S E E I N S T R U C T I O N S
S E R . N o .
Fig. 8 Typical Circuit Breaker Nameplate
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
T O S H I B A
V A C U U M C I R C U I T B R E A K E R
T Y P E
H V 6 F S -
7 . 2 /4 . 8 k V , R M S
5 0 / 6 0 H z
6 3 0 A , R M S
6 0 k V , C R E S T
2 2 k V A C R M S
2 4
k g
5 3
l b s
0 2 7 0 0 2 2 1
T O S H I B A I N T E R N A T I O N A L C O R P O R A T I O N
H O U S T O N , T E X A S U . S . A .
at the installation location, a space heater should
be installed inside the circuit breaker enclosure.
NOTE:
Temperature,
conditions outside of the usual limits
may require derating or other special
equipment.
Toshiba representative for additional
information.

RATING VERIFICATION

Prior to Installation, the maximum fault current
capacity of the power system at the point of
installation should be verified. This value must
not
exceed
the
capability of the circuit breaker.
illustrates a typical circuit breaker nameplate.
Do not exceed the ratings
DANGER
specified on the circuit
breaker nameplate or
system accessories.
Underrated equipment can
fail during operation
causing fire, explosion,
severe injury, death, and
property damage.
M U - V V
S H O R T C K T . A M P S
I N T E R R U P T I N G T I M E
C L O S E V O L T S
S H U N T T R I P V O L T S
U V T R I P V O L T S
M F G . S T A N D A R D
G F 0 7 Z 3 0 3
M F G . D A T E
7 / 0 2

INSTALLATION

altitude
or
other
Contact
your
nearest
symmetrical
interrupting
Fig. 8
1 4 / 1 6 k A , R M S
3 C Y C L E S
1 2 5
V D C
1 2 5
V D C
1 2 0 V A C
J I S C 4 6 0 3 - 1 9 9 0
J E C - 2 3 0 0 - 1 9 8 5