Mitsubishi Electric PUZ-A18NHA2 Service Manual page 89

Split-type, heat pump air conditioners
Table of Contents

Advertisement

(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number.
Function
Filter sign
100h
2500h
"Clean the filter" indicator is not displayed
Air flow
Quiet
( Fan speed )
Standard
High ceiling
No.of air outlets
4 directions
3 directions
2 directions
Optional high efficiency
Not supported
filter
Supported
No vanes (Vane No.3 setting : PLA only)
Vane setting
Vane No.1 setting
Vane No.2 setting
Disabled
Energy saving air
flow ( Heating mode )
Enabled
Not supported
Optional humidifier
( PLA only )
Supported
No.1 setting (TH5: 24-28:)
Vane differential setting
No.2 setting (Standard, TH5:28-32:)
in heating mode
( cold wind prevention )
No.3 setting (TH5: 32-38:)
Swing
Not available Swing
Available
Available
Set temperature in heating
mode ( 4 deg up )
Not available Temperature correction: Invalid
Extra low
Fan speed when the
Stop
heating thermostat is OFF
Keeping fan speed set by remote controller
Disabled (Standard)
Quiet operation mode
of PLA-AA ( Fan speed )
Enabled (Quiet operation mode)
Keeping fan speed set by remote controller
Fan speed when the
cooling thermostat is OFF
Stop
Detect
Detection of abnormality of
the pipe temperature ( P8 )
Neglect
Mode No.11
Setting No.
Settings
Vane No.3 setting
1
No Vanes
2
Vane No.1 setting
3
Vane No.2 setting
* Be careful of the smudge on ceiling.
Mode
Settings
No.
07
08
09
10
11
12
13
14
}
PLA-BA
23
Wave air flow
Temperature correction: Valid
}
PLA-BA
24
25
26
27
28
PLA-BA
Less smudging
( Downward position than the standard )
Standard
Less draft *
( Upward position than the standard )
89
: Initial setting ( Factory setting )
4-Way
Setting
Ceiling suspended
No.
cassette
PLA-BA
1
2
3
1
2
3
1
2
3
1
2
1
2
3
1
-
2
-
1
2
1
2
3
1
2
1
2
1
2
3
1
-
2
-
1
2
1
2
No vane function
Standard
Less draft *
( Upward position than the standard )
- : Not available
Wall
mounted
PKA-GA(L)
PCA-GA
PKA-FA(L)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PCA-GA